Download Print this page

Voltage Regulation - Tripp Lite SmartOnline SUINT3000RTXL2U Manual

Smartonline 3kva on-line double-conversion ups, 2u rack/tower, 200/208/220/230/240v c13/c19 outlets
Hide thumbs Also See for SmartOnline SUINT3000RTXL2U:

Advertisement

VOLTAGE REGULATION

Voltage regulation
Online, double-conversion power conditioning
description
Overvoltage
2% output voltage regulation during overvoltages to 288
correction
Undervoltage
2% output voltage regulation during undervoltages to 160V
correction
Severe undervoltage
2% output voltage regulation during undervoltages to 140V (under 66% load only) or 120V (under 33% load only)
correction
LEDS ALARMS & SWITCHES
LED Indicators
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery
and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in
rack/tower formats
Alarms
Audible alarm indicates power failure, low battery, overload, replace battery and EPO operation
Alarm cancel
Power-fail alarm can be silenced using alarm-cancel switch
operation
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION
UPS AC suppression
420 joules
joule rating
EMI / RFI AC noise
Yes
suppression
AC suppression
Instantaneous
response time
PHYSICAL
Installation form
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
factors supported
with optional
accessories
Primary form factor
Rackmount
UPS / Power Module
3.5 x 17.3 x 26
dimensions in
primary form factor
(height x width x
depth / inches)
UPS / Power Module
8.9 x 43.9 x 66
dimensions in
primary form factor
(height x width x
depth / cm)
Rack Height
2U
Secondary form factor
Tower (requires 2-9USTAND)
UPS / Power Module
70.5
weight (lbs)
UPS / Power Module
32
weight (kg)
UPS Shipping
9 x 22 x 32.8
dimensions (height x
width x depth / inches)

Advertisement

loading