Recommended
120V 30A dedicated circuit
Electrical Service
BATTERY
Full load runtime
6 minutes (2400 watts) - expandable
Half load runtime
17 minutes (1200 watts) - expandable
Expandable
Supports extended runtime with optional external battery packs BP72V28-3UNAFTA (multi-pack compatible)
battery runtime
DC system voltage
72VDC
Typical battery
3-6 years, depending on usage
lifespan
Battery recharge
less than 6 hours to 80%
rate
Replacement
RBC96-3U (qty 1)
Battery Cartridge

VOLTAGE REGULATION

Voltage regulation
On-line, double-conversion power conditioning maintains output within 2% of 110/120 volts at all times
description
Overvoltage
Maintains output of selected nominal +/-2% during overvoltages to 138V AC
correction
Brownout
Maintains output of selected nominal +/-2% during undervoltages to 65V AC (at loads greater than 70% undervoltage
correction
correction extends to 80V)
LEDS ALARMS & SWITCHES
Front panel LEDs
LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red), battery
low (yellow) - 4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%).
Alarms
Multi-function audible alarm with distinctive ring patterns offer notification of backup operation (2 seconds on / 0.5 seconds
off), low battery warning (1.25 seconds on / 0.5 seconds off), overload (sounds continuously), UPS fault (4.2 seconds on /
1 second off), input voltage out of frequency (2.1 seconds on / 0.14 seconds off) and high input voltage (2.1 seconds on
0.07 seconds off)
Switches
Includes power off/on switch to enable system turn on (press ON switch), UPS battery test (press ON switch during normal
AC operation), buzzer silence (press ON switch during battery operation) and OFF (press OFF switch). All switch functions
require that the switch be pressed and held for longer than 2 seconds, but less than 4 seconds
SURGE / NOISE SUPPRESSION
AC surge
480 joules
suppression
AC suppression
Instantaneous
response time
Dataline
Set of 8 wire RJ style interface jacks offer surge suppression for network ethernet or TEL/DSL connection. Pins 1,2,3 and
suppression
6 offer ethernet protection starting at 7.5V and the center two wires, pins 4 & 5, offer TEL/DSL line suppression starting at
260V
EMI / RFI AC noise
Yes
suppression
PHYSICAL
Shipping weight
75.2
(lbs)
Shipping weight
34.1
(kg)
Shipping
15.25 x 13 x 24
Dimensions
(HWD/in)
Shipping
38.7 x 33 x 61
Dimensions
(HWD/cm)
Unit weight (lbs)
69.3
Unit weight (kg)
31.5