Download Print this page

Voltage Regulation - Tripp Lite SmartOnline SU3000RTXL3UHV Specifications

Smartonline expandable rack / tower ups system - online, double-conversion protection for mission critical applications
Hide thumbs Also See for SmartOnline SU3000RTXL3UHV:

Advertisement

Expandable battery
Supports extended runtime with optional external battery pack BP72V15-2U (limit 1), BP72V28-3U (multi-pack
runtime
compatible)
DC system voltage
72 V DC
Typical battery
3-6 years, depending on usage
lifespan
Battery recharge
2-4 hours to 90%
rate

VOLTAGE REGULATION

Voltage regulation
On-line, double-conversion power conditioning maintains output within 2% of 200/208/220/230/240 volts at all times
description
Overvoltage
Maintains output during overvoltages to 275V AC
correction
Brownout
Maintains output during undervoltages to 160V AC
correction
Severe brownout
At load levels less than 70%, UPS maintains output during undervoltages to 130V AC
correction
LEDS ALARMS & SWITCHES
Front panel LEDs
6 LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red), battery
low (yellow)
4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%)
Alarms
Multi-function audible alarm offers notification of UPS start, backup operation, low battery warning, overload, UPS fault
and remote shutdown
Switches
Includes main power off/on switch, plus 1 switch to select battery charge / load level display
SURGE / NOISE SUPPRESSION
AC surge
2670 joules
suppression
AC suppression
Instantaneous
response time
EMI / RFI AC noise
Yes
suppression
PHYSICAL
Shipping weight
90.3
(lbs)
Shipping weight
41.0
(kg)
Shipping
13.3 x 23.8 x 25.7
Dimensions
(HWD/in)
Shipping
33.8 x 60.5 x 65.3
Dimensions
(HWD/cm)
Unit weight (lbs)
74.9
Unit weight (kg)
34.0
Unit Dimensions
5.2 x 17.3 x 19.8
(HWD/in)
Unit Dimensions
13.3 x 44.5 x 50.3
(HWD/cm)
Material of
Steel
construction
Form factors
Rack (3U)
supported
Cooling method
Built-in cooling fan

Advertisement