GE EPM 5300 Instruction Manual page 61

Digital multifunction power monitors
Table of Contents

Advertisement

HOW TO USE KYZ PULSE VALUE TABLE FOR MULTIPLICATION:
S
1: FSW=9999.
ITUATION
Selection is Multiply by 2
This means that every .5 unit WH =1 pulse.
Unit=Kilo (see Group 1, Function 2)
Result: For every 1 KWH increment on the
counter, the meter will output 2 pulses.
S
3: FSW=99.99
ITUATION
Selection is Multiply by 20
This means that every .0005 unit WH=1 pulse.
Unit=Kilo (see Group 1, Function 2)
Result: For every 1 KWH increment on the
counter, the meter will output 2,000 pulses.
HOW TO USE THE KYZ PULSE VALUE TABLE FOR DIVISION:
S
1: FSW=9999.
ITUATION
Selection is Divide by 10
This means that every 10 unit WH=1 pulse.
Unit=Kilo (see Group 1, Function 2)
Result: For every 10 KWH increment on the
counter, the meter will output 1 pulse.
S
3: FSW=99.99
ITUATION
Selection is Divide by 20
This means that every .2 unit WH=1 pulse.
Unit=Kilo (see Group 1, Function 2)
Result: For every 1 KWH increment on the
counter, the meter will output 5 pulses.
To change the KYZ pulse value:
AC VOLTS
MAX
A
B
MIN
N
N
LM1
LM2
AC AMPS
A
POWER
KVAH
KWH
FREQ
MAX/MIN
PHASE
VOLTS AMPS
POWER
LIMITS
Step 1:
a. Enter Group Level of
Programming Mode, (see Chp. 8).
b. Press MAX/MIN/LIMITS until 0.
appears in upper display.
c. Press AMPS to activate the
Group.
GE Multilin
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP
MAX
C
A
B
C
MIN
N
B
C
A
LM1
LM2
B
C
N
PF
KW
KVA
KVAR
KVAH
MAX/MIN
LIMITS
NEXT
Step 2:
a. Press MAX/MIN/LIMITS until 06.P
appears in upper display.
! The lower display indicates
multiplication or division factor.
EPM 5000 series Advanced Power Meters
S
2: FSW=999.9
ITUATION
Selection is Multiply by 2
This means that every .05 unit WH=1 pulse.
Unit=Kilo (see Group 1, Function 2)
Result: For every 1 KWH increment on the
counter, the meter will output 20 pulses.
S
4: FSW=9.999
ITUATION
Selection is Multiply by 20
Unit=Kilo (see Group 1, Function 2)
This means that every .00005 WH=1 pulse.
Result: For every 1 KWH increment on the
counter, the meter will output 20,000 pulses.
S
2: FSW=999.9
ITUATION
Selection is Divide by 10
This means that every 1 unit WH=1 pulse.
Unit=Kilo (see Group 1, Function 2)
Result: For every 1 KWH increment on the
counter, the meter will output 1 pulse.
S
4: FSW=9.999
ITUATION
Selection is Divide by 20
Unit=Kilo (see Group 1, Function 2)
This means that every .02 WH=1 pulse.
Result: For every 1 KWH increment on the
counter, the meter will output 50 pulses.
AC VOLTS
A
B
C
A
B
C
N
N
N
B
C
A
AC AMPS
A
B
C
N
POWER
PF
KW
KVA
FREQ
KVAR
KWH
PHASE
VOLTS AMPS
POWER
NEXT
AC VOLTS
MAX
A
B
MIN
N
N
LM1
LM2
AC AMPS
A
POWER
KVAH
KWH
FREQ
MAX/MIN
PHASE
VOLTS AMPS
POWER
LIMITS
Step 3:
a. Press AMPS to change current
setting.
! The decimal point next to the 6
disappears.
b. Press MAX/MIN/LIMITS to
advance selections. -or-
c. Press VOLTS to reverse.
(Until desired factor appears).
! Division is indicated by div
appearing in the middle display.
When middle display is blank, it
indicates multiplication.
d. Press AMPS to store.
C
A
B
C
N
B
C
A
B
C
N
PF
KW
KVA
KVAR
NEXT
57