CHAPTER 3: ELECTRICAL INSTALLATION
Note: Unless otherwise specified, standard KYZ setup for Pulse Output 0 is positive Watt Hour,
Pulse Output 1 is negative Watt-Hour, and Pulse Output 2 is VA-hour. See table below for
standard rate.
Note: With Option R (available only with the EPM 5200P) the setup for Pulse Output 0 is positive
Watt-Hour, Pulse output 1 is positive VAR-hour, and Pulse output 2 is negative VAR-hour.
The scale factor for Wattage (KW or MW) and Full Scale Decimal Point Placement is selectable in
Programming Mode GROUP 1, FUNCTION 2. Follow the Decimal Point Placement corresponding to the
Change in Level. A multiplication or division factor can be programmed. See Programming GROUP 0,
FUNCTION 6 for a different rate.
DECIMAL POINT PLACEMENT
*Units could be KiloWatts or MegaWatts.
KYZ relay output (Form C), rated 200V, 100mA: 3 separate KYZ Outputs (labeled 0 through 2).
16
STANDARD RATE TABLE FOR WATTS
(KW/MW)
9999.0
999.9
99.99
9.999
2 0
K
2 1
Y
2 2
Z
2 3
K
2 4
Y
2 5
Z
2 6
K
2 7
Y
2 8
Z
Figure 3.2: KYZ Relay Connection for -NL2 Option
EPM 5000 series Advanced Power Meters
*
CHANGE IN LEVEL
1.0 Units W Hour
0.1 Units W Hour
0.01 Units W Hour
0.001 Units W Hour
P U L S E
O U T P U T 2
P U L S E
O U T P U T 1
P U L S E
O U T P U T 0
GE Multilin