GE EPM 5300 Instruction Manual page 51

Digital multifunction power monitors
Table of Contents

Advertisement

PACK
SWITCH
A
B
0
C
D
A
B
1
C
D
A
B
Power Factor Polarity Indicates + (voltage referenced)
2
C, D
For EI-BUS protocol: Switch C is DOWN, Switch D is DOWN.
For MODBUS protocol, ASCII framing: Switch C is UP, Switch D is UP.
For MODBUS protocol, RTU framing: Switch C is DOWN Switch D is UP.
For DNP 3.0 protocol: Switch C is UP, Switch D is DOWN.
A
(Relay Control 1 and 2 apply only if Relay Option -NL
3
B
(Relay Control 1 and 2 apply only if Relay Option -NL
C
D
Table 9-2: System Configuration—Switch Packs for Group 0, Function 3
GE Multilin
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP
FEATURE
Reserved
Reserved
Reserved
Phase Reversal Limit Detection
Non-significant will blank leading zero
Reset Protection
(see Part I: Installation and Operation)
Phase Reversal Rotation Selection
Open Delta Installation
(see Part I: Installation and Operation)
Limit/Relay Control
- (current referenced)
Trip Relay Computer Control 1
was ordered.)
Trip Relay Computer Control 2
was ordered.)
RS-232 or RS-485 Communications or Print
DC Output
(To operate DC Output, disable PACK 3, Switch C)
Print Operating and Programming Data
(To print, set PACK 3 Switches C and D to UP
position.)
EPM 5000 series Advanced Power Meters
or
or
SEGMENT POSITION
UP: Enable
DOWN: Disable
UP: Enable
DOWN: Disable
UP: Enable
DOWN: Disable
UP: CBA Rotation
DOWN: ABC Rotation
UP: Enable
DOWN: Disable
UP: Average
DOWN: Instantaneous
UP: -PF
DOWN: +PF
UP: Enable
DOWN: Disable
UP: Enable
DOWN: Disable
UP: Enable Communications
DOWN: Enable DC Output
UP: Enable DC Output or Print
Communication
DOWN: Disable DC Output and
Print
47