3.5 Precautions when Wiring Ethernet Port (GT32T1)

Although more than one GT32T1 can be connected using a hub, communication is performed with one
-
unit each. Specify each destination to communicate.
Use a UTP cable (unshielded cable) for the Ethernet cable, and take measures for noises such as
-
installing a ferrite core if necessary.
It conforms to CE marking. As conditions, the following wiring is required.
-
1. Do not use a shield wire for the Ethernet cable.
2. Install a ferrite core to the Ethernet cable and make one turn.
(Recommended ferrite core: Kitagawa Industries SFC-10 or equivalent)
GT32T1
Key Point:
The CE marking standards that the GT32 conforms to
European EMC directive 2004/108/EC
European EMC standards (EN61131-2)