5.3.5 When Connected to a PLC Made by Omron Corporation

For GT01, GT11 and GT21
Code No.
Content
Time up error
ER00
There is no response
from the PLC.
Cannot be executed
due to operation mode.
(The PLC received the
ER01
command that cannot
be executed in the
operation mode.)
Data error
ER10
A data error occurred
during communication
Overrun error
ER12
The GT cannot receive
data.
Numerical data error
ER15
Designated read/write
area is wrong.
• Error codes other than these are based on Omron PLC error codes.
• Be sure to used the PLC in monitor mode. Otherwise, communication will not work properly.
For GT02, GT02L, GT05, GT12, GT32 and GT32-E
Code No.
Content
Cannot be executed
due to operation mode.
(The PLC received the
ER0001
command that cannot
be executed in the
operation mode.)
Data error
ER0010
A data error occurred
during communication
Overrun error
ER0012
The GT cannot receive
data.
Numerical data error
ER0015
Designated read/write
area is wrong.
• Error codes other than these are based on Omron PLC error codes.
• Be sure to used the PLC in monitor mode. Otherwise, communication will not work properly.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Cause and solution
1) PLC connection cable is disconnected. Check the wiring of
the connection cable and check for disconnection.
2) It is a temporary error caused by noise, etc. Turn on the
power supplies for PLC or GT again.
Change the mode of the PLC from the operation mode to the
monitor mode.
Check for errors in the communication conditions settings.
PLC runaway might be the problem.
Verify whether or not the reference device used with the basic
communication area and each part is a readable and writable
area.
Cause and solution
Change the mode of the PLC from the operation mode to the
monitor mode.
Check for errors in the communication conditions settings.
PLC runaway might be the problem.
Verify whether or not the reference device used with the basic
communication area and each part is a readable and writable
area.