Masonry And Factory Built Fireplace Clearances; How To Determine If Alternate; Floor Protection Materials Are Acceptable - Regency I1200 Owners & Installation Manual

Wood insert
Hide thumbs Also See for I1200:
Table of Contents

Advertisement

INSTALLATION

MASONRY AND FACTORY BUILT FIREPLACE CLEARANCES

The minimum required clearances to combustible materials when installed into a masonry or factory built fi replace are listed below.
Adjacent
Unit
Side Wall
(to Side)
A
I1200S
15" (381mm) 20" (508mm)
Side and Top facing is a maximum of 1.5" thick.
Floor protection must non-combustible, insulative
material with an R value of 1.1 or greater.
*
If the hearth extension is fl ush with the fl oor (F)
it must extend 19.5" in front of the body face
(E).
Note: Hearth Extension Width (G) is meas-
ured from edge of fuel door to side of
hearth.
** A non-combustible mantel may be installed
at a lower height if the framing is made of
metal studs covered with a non-combustible
board.
Thermal fl oor protection is not required if the unit is
raised 3.5" minimum (measured from the bottom of
the stove). However, standard ember fl oor protection
is required. It will need to be a non-combustible mate-
rial that covers 16" (406 mm) in the US and 18" (450
mm) in Canada to the front of the unit and 8" (200
mm) to the sides.
If the unit is not raised, thermal fl oor protection required
is 18" (450 mm) in the US and Canada.

FLOOR PROTECTION MATERIALS ARE ACCEPTABLE

The specifi ed fl oor protector should be 3/8"
(18mm) thick material with a K - factor of
0.84.
The proposed alternative is 4" (100mm) brick
with a C-factor of 1.25 over 1/8" (3mm) mineral
board with a K-factor of 0.29.
Step (a):
Use formula above to convert specifi cation
to R-value.
R = 1/k x T = 1/0.84 x .75 = 0.893.
8
Mantle**
Top
(to Top)
Facing
(to Top)
B
C
14" (356mm) 7.375"(187mm) 16" (406mm) 1.5" (38mm)
Please check to ensure that your fl oor protection and hearth will meet the standards for
clearance to combustibles. Your hearth extension must be made from a non-combustible
material.

HOW TO DETERMINE IF ALTERNATE

Step (b):
Calculate R of proposed system.
4" brick of C = 1.25, therefore
Rbrick = 1/C = 1/1.25 = 0.80
1/8" mineral board of k = 0.29, therefore
Rmin.bd. = 1/0.29 x 0.125 = 0.431
Total R = Rbrick + Rmineral board =
0.8 + 0.431 = 1.231.
Step (c):
Compare proposed system R of 1.231 to
specifi ed R of 0.893. Since proposed system
R is greater than required, the system is
acceptable.
Side
Minimum
Facing
Hearth
(to Side)
Extension*
D
E
Clearance diagram for installations
Floor Protection
DEFINITIONS
Thermal Conductance:
C
Thermal Conductivity:
k =
3
(hr)(ft
Thermal Resistance:
R = (ft
Minimum
Minimum
Hearth
Hearth Side
Thickness*
Extension
F
G
8" (203mm)
=
Btu
=
W
(hr)(ft
2
)(
o
F)
(m
2)
)(K)
(Btu)(inch)
=
W
=
Btu
o
o
)(
F)
(m)(K)
(hr)(ft)(
F)
2
)(hr)(
o
F)
=
(m
2
)(K)
Btu
W
I1200 Regency Wood Insert