Checking Co Content And Setting If Necessary (Setting The Air Figure); Checking The Equipment Function - Vaillant ecoTEC exclusive 832 Installation And Maintenance Instructions Manual

Gas wall boilers with condensing appliance technology
Table of Contents

Advertisement

6 Start-up
If the connection pressure is not within the permissible
range and you cannot resolve the problem, inform the
gas supply authority. Proceed as follows:
Take the appliance out of operation.
• Close the gas isolation cock on the unit.
• Remove the pressure gauge and screw the sealing
screw (1) back in again.
• Make sure that the sealing screw is not leaking.
Put the front casing back on.
Do not start up the appliance!
6.2.3 Checking CO
content and setting if neces-
2
sary (setting the air figure)
• Remove the front cover.
• Activate test programme P.1 (see Chapter 9.2).
• Wait at least 5 minutes until the appliance reaches
its operating temperature.
1
2
3
4
Fig. 6.6 Checking/adjusting the CO
• Measure the CO
content on the flue gas measuring
2
nozzles (1). Compare the measured value with the
corresponding value in Table. 6.4.
• If the CO
content needs to be adjusted, release the
2
screw (3) and hinge the air intake pipe (2) through
90° to the front. Do not remove the air intake pipe!
• If necessary, set the corresponding CO
(value with removed appliance front, see Table 6.4)
by turning the screw (4) in.
26
content
2
content
2
- Turning to the left: higher CO
- Turning to the right: lower CO
h
Note!
Natural gas: Adjust only in increments of 1/8
turn and wait approx. 1 minute after each ad-
justment until the value stabilises.
h
Note!
Liquid gas: Adjust only in increments of 1/16
turn and wait approx. 1 minute after each ad-
justment until the value stabilises.
• After completion of the setting process, hinge the air
intake pipe back up.
• Check the CO
content again.
2
• If necessary, repeat the setting process.
• Press the "i" button. The "Full load mode" is turned
off. The full load mode is also exited if no button is
pushed for 15 minutes.
• Re-secure the air intake pipe with the screw (3).
• Put the front casing back on.
Settings
CO
after 5 minutes full load
2
mode with front casing re-
moved
set for Wobbe-Index W
0
Table 6.4 Factory gas settings
6.3

Checking the equipment function

After installing and checking the gas supply pressure,
perform a function check before commissioning the ap-
pliance and handing over to the user.
• Commission the appliance in accordance with the in-
structions in the relevant operating manual.
• Check the gas infeed, exhaust gas installation, boiler and
heating installation and the hot water pipes for leaks.
• Check the flue pipe for proper installation.
• Check over-ignition and that the flame on the burner
is burning evenly.
• Check the function of the heating (see Chapter 6.3.1)
and the hot water preparation (see Chapter 6.3.2)
• Hand the unit over to the user.
The Vaillant ecoTEC exclusive has status codes which
indicate the operating condition of the appliance in the
display. Functional checks of the hot water and heating
operation can be undertaken using these status codes
by pushing the button "i".
ecoTEC exclusive installation and maintenance instructions / 0020017768_04
content,
2
content,
2
Natural
Propane
gas H
Unit
Tolerance
Tolerance
9,0 +/- 1,0 10,0 +/- 0,5 Vol.–%
kWh/
12,4
22,5
m3