Installation — Electrical
2. Isolated 2-10 VDC Voltage Source Input.
Set DIP Switch SW1-1 of Options Module 1U2 to "OFF" . Connect the voltage
source to terminals TB1-4 (+) and TB1-5 (-) on Options Module IU2. CWS is
now based on the following equation:
CW Setpoint °F = (VDC x 125) - 16.25
Sample values for CWS vs. VDC signals are shown in
Minimum setpoint = 0 F(2.0 VDC input )
Maximum setpoint = 65 F ( 9.4 VDC input )
Maximum continuous input voltage = 15 VDC
Input impedance (SW1-1 on) = 40.1 Kohms
3. Isolated 4-20 mA Current Source Input.
Set DIP Switch SW1-1 of Options Module 1U2 to "ON" . Connect the current
source to terminals TB1-4 (+) and TB1-5 (-). CWS is now based on the
following equation:
Setpoint °F = (mA x 4.0625) - 16.25
Sample values for CWS vs., mA signals are shown in
Minimum setpoint = 0F(40mA)
Maximum setpoint = 65 F (18.8 mA)
Maximum continuous input voltage = 30 mA
Input impedance (SW1-1 off) = 499 ohms
NOTE: The negative terminal TB1 -5 is referenced to the UCM chassis
ground. To assure correct operation, 2-10 VDC or 4-20 mA signals must be
isolated or "floating" with respect to the UCM chassis ground.
Table 14

Input Values Vs. External Chilled Water Setpoint

Inputs
Resistance (Ohms)
Current (ma)
944330
4.0
686092
5.2
52946
6.5
42434
7 .7
34889
8.9
29212
10.2
24785
11.4
21236
12.6
18327
13.8
15900
15.1
13844
16.3
12080
17 .5
10549
18.8
9050
20.0
Table
14.
Table
14.
Resulting Chilled
Voltage (Vdc)
Water Setpoint (F)
2.0
0.0
2.6
5.0
3.2
10.0
3.9
15.0
4.5
20.0
5.1
25.0
5.7
30.0
6.3
35.0
6.9
40.0
7 .6
45.0
8.2
50.0
8.8
55.0
9.4
60.0
10.0
65.0