Table PD-38— Supply Fan Performance With VARIABLE FREQUENCY DRIVE or WITHOUT INLET VANES — 60, 70 and 75 Tons
Cfm
Std
.250
Air
RPM
BHP
RPM
14000
295
1.55
366
15000
305
1.80
373
16000
316
2.08
380
17000
327
2.38
389
18000
338
2.72
399
19000
349
3.09
408
20000
361
3.48
419
21000
372
3.91
429
22000
384
4.37
440
23000
395
4.87
450
24000
407
5.41
461
25000
419
5.98
473
26000
431
6.60
484
27000
443
7.26
495
Cfm
Std
2.250
Air
RPM
BHP
RPM
14000
723
10.67
757
15000
730
11.32
764
16000
736
11.96
771
17000
741
12.57
777
18000
746
13.17
782
19000
751
13.76
787
20000
755
14.36
791
21000
758
14.97
795
22000
761
15.64
799
23000
762
16.37
801
24000
764
17.14
803
25000
765
17.94
805
26000
766
18.72
806
27000
768
19.51
807
Cfm
Std
4.250
Air
RPM
BHP
RPM
14000
947
21.47
970
15000
957
22.59
981
16000
967
23.75
991
17000
976
24.94
1000
18000
985
26.17
1009
19000
992
27.40
1017
20000
999
28.63
1024
21000
1006
29.85
1031
22000
1012
31.04
1037
23000
1017
32.21
1043
24000
1022
33.35
1048
25000
1027
34.48
1053
26000
1031
35.60
1058
27000
1036
36.71
1062
Notes:
1. Fan performance for 60, 70 and 75 ton rooftops are identical. However, note maximum motor hp size for each size. Contact your local Trane representative for information on
non-standard motors.
2. Shaded areas at table extremes note non-standard Bhp or Rpm selection. Contact your local Trane representative for more information.
3. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component