Evaporator Fan Performance 12½ Tons With Gas Heat Ycd151C Standard Or Txv Refrigeration System Downflow; Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm; 3-Hp Standard Motor & High Static Drive Accessory; External Static Pressure (Inches Of Water) - Trane Voyager TC* User Manual

Packaged cooling & gas/electric rooftops 12 1/2-25 tons — 60 hz
Table of Contents

Advertisement

Table 35.
Evaporator Fan Performance 12½ Tons with Gas Heat YCD151C Standard or TXV Refrigeration System Downflow
.10
.20
CFM
RPM
BHP
RPM
BHP
3-HP Standard Motor & Field Supplied Low Static Drive
4000
497
0.75
4500
531
0.96
5000
506
0.98
565
1.21
5500
544
1.24
600
1.51
6000
582
1.55
636
1.84
Continued
1.10
1.20
CFM
RPM
BHP
RPM
BHP
3-HP Standard Motor & Drive
4000
841
2.09
869
2.23
4500
869
2.52
896
2.68
5000
897
2.99
924
3.17
5500
925
3.52
952
3.72
6000
955
4.09
981
4.32 1007 4.54 1032 4.77 1056 4.99 1080 5.21 1103 5.42 1125 5.64
For Standard Evaporator Fan Speed (RPM), reference
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference
For Oversized Evaporator Fan Speed (RPM), reference
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to
Table 54
to determine additional static pressure drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i)
Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be necessary.
RT-PRC024-EN
Performance Data

External Static Pressure (Inches of Water)

.30
.40
.50
RPM
BHP
RPM
BHP
RPM
551
0.92
598
1.08
641
583
1.16
629
1.34
671
616
1.43
661
1.65
701
649
1.76
693
2.00
733
684
2.12
726
2.39
765
3-HP Standard Motor & High Static Drive Accessory
External Static Pressure (Inches of Water)
1.30
1.40
1.50
RPM
BHP
RPM
BHP
RPM
896
2.36
922
2.50
947
923
2.84
948
2.99
973
950
3.35
976
3.53 1000 3.71 1024 3.88 1047 4.05 1070 4.22
978
3.92 1004 4.12 1028 4.32 1052 4.51 1075 4.71 1097 4.90
5-HP Oversized Motor & Drive
Table
50.
Table
53.
(12½ Tons High Efficiency)
.60
.70
BHP
RPM
BHP
RPM
BHP
(i)
3-HP Standard Motor & Drive
1.23
680
1.38
716
1.53
1.52
709
1.70
745
1.87
1.85
739
2.05
774
2.25
2.23
770
2.45
804
2.67
2.65
801
2.90
835
3.15
1.60
1.70
BHP
RPM
BHP
RPM
BHP
3-HP Standard Motor & High Static Drive Accessory
2.63
971
2.76
994
2.89 1016 3.04
3.14
997
3.30 1020 3.45 1043 3.60
Table
51.
.80
.90
RPM
BHP
RPM
BHP
RPM
750
1.67
782
1.82
812
778
2.03
810
2.20
840
807
2.44
838
2.63
868
837
2.89
868
3.10
897
867
3.39
898
3.63
927
5-HP Oversized Motor & Drive
1.80
1.90
RPM
BHP
RPM
BHP
RPM
1037 3.19
1059
1065 3.75
1087
1092 4.39
1113
1119 5.09
1140
1.00
BHP
1.96
2.36
2.81
3.31
3.86
2.00
BHP
3.35
3.89
4.56
5.28
53

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Voyager yc*Voyager tc seriesVoyager yc series

Table of Contents