Manual Control Settings - Trane AdaptiView Operation Manual

For gear-driven water-cooled centravac (cvgf) chillers
Table of Contents

Advertisement

Equipment Settings
Table 9.

Manual Control Settings

Table 10, p.
screen, along with their corresponding setting options. The chiller configuration determines which
of the settings appear.
Table 10. Manual Control settings menu screen: Buttons, available setting options, and status points
Feature
Chiller Control Signal
Evaporator Pump Override
Condenser Pump Override
Head Pressure Control Override
Clear Energy Consumption
Oil Pump Control
Clear Restart Inhibit
42
Chilled Water Reset menu screen: Buttons and available setting options (continued)
Buttons
Outdoor Start Reset
Outdoor Maximum Reset
42, lists the settings that are available as buttons on the Manual Control Settings menu
Current value
Auto/Manual
On/Off
On/Off
Auto/Manual
XXXX kWh
On/Off
XX:XX min:sec
Available setting options
Valid numerical range appears on screen.
Valid numerical range appears on screen.
Available setting
options
Manual mode: Up/down
arrows for changing the
setpoint
• Auto
• On
• Auto
• On
Manual mode: Up/down
arrows for changing the
value
• Clear
• Auto
• On
• Clear
Status points
• IGV1 Position
• IGV2 Position
• Average Line Current
• AFD Frequency
• Active Chilled Water Setpoint (Active Hot Water
Setpoint if in Heating mode)
• Evap Leaving Water Temp (Cond Leaving Water
Temp if in Heating mode)
• Evaporator Pump Manual Override Time Remaining
• Evap Water Flow Switch Status
• Active Chilled Water Setpoint
• Evap Leaving Water Temp
• Condenser Pump Manual Override Time Remaining
• Cond Water flow Switch Status
• Active Hot Water Setpoint
• Cond Leaving Water Temp
• Condenser Entering Water Temperature
• Condenser Leaving Water Temperature
• Condenser Refrigerant Pressure
• Average Line Current
• Condenser Water Flow
• Approximate Condenser Water Flow
• Evaporator Refrigerant Pressure
• Differential Refrigerant Pressure
• Oil Pump Manual Override Time Remaining
• Oil Differential Pressure
• Oil Pump Discharge Pressure
• Oil Tank Pressure
Motor Winding Temperature #1
Motor Winding Temperature #2
Motor Winding Temperature #3
CTV-SVU02A-EN