Viessmann VITOROND 200 Technical Data Manual page 9

Oil-/gas-fired boiler, triple-pass hot water heating boiler 490 to 1096 mbh / 144 to 321 kw
Hide thumbs Also See for VITOROND 200:
Table of Contents

Advertisement

Recommended Minimum Service Clearances
39½" /
19¾" /
500 mm
1000 mm
19¾" /
500 mm
Recommended Clearances to Combustibles
Boiler model
VD2-
Top
Sides
Flue (oil)
Flue (gas)
Front
Floor
IMPORTANT
Maintain 1" air clearance from uninsulated
hot water pipes to combustible material.
IMPORTANT
Boiler must not be installed on carpet.
VITOROND 200, VD2
The combustion chamber door is factory assembled to hinge on the left-hand
side. A right-hand hinge is feasible by rebuilding the door hinge hardware.
c
Boiler model
c
d
Inch dimensions rounded to the nearest ¼".
Front clearances (dimension "c" above) will allow for easy removal of flue gas
turbulator inserts, as well as for full insertion of bristle brush for heat exchanger
d
cleaning.
8" / 200 mm
IMPORTANT
Minimum side clearance of 19¾" / 500 mm
must be maintained for side-mounted KR or
Dekamatik controls.
125
VD2-125
VD2-160
inches
47¼
mm
1200
inches
Dependent on burner model
mm
160
Technical Data
VD2-195
VD2-230
53
59
1350
1500
1650
195
230
VD2-270
65
71
1800
270
6" / 150 mm
6" / 150 mm
9" / 229 mm
6" / 150 mm
6" / 150 mm
non-combustible