Water Quality; Electrical Requirements - Viessmann VITOROND 200 Technical Data Manual

Oil-/gas-fired boiler, triple-pass hot water heating boiler 490 to 1096 mbh / 144 to 321 kw
Hide thumbs Also See for VITOROND 200:
Table of Contents

Advertisement

System Design Considerations/Burner Alternatives
System Design Considerations

Water quality

Treatment for boiler feed water should be
considered in areas of known problems,
such as where a high mineral content and
hardness exist. In areas where freezing
might occur, an antifreeze may be added to
the system water to protect the system.
Please adhere to the specifications given by
the antifreeze manufacturer. Do not use
automotive silicate-based antifreeze. Please
observe that an antifreeze/water mixture
may require a backflow preventer within the
automatic water feed and influence
components such as diaphragm expansion
tanks, radiation, etc. A 40% antifreeze
content will provide freeze-up protection to
-10°F / -23°C. Do not use antifreeze other
than specifically made for hot water heating
systems. System also may contain
components which might be negatively
affected by antifreeze. Check total system
frequently when filled with antifreeze.
Follow the instructions of antifreeze
manufacturer.
Oxygen diffusion barrier
underfloor tubing
The boiler warranty does not cover leaks
resulting from corrosion caused by the use
of underfloor plastic tubing without an
oxygen diffusion barrier. Such systems must
have the tubing without oxygen diffusion
barrier separated from the boiler with a heat
exchanger. Viessmann recommends the use
of underfloor plastic tubing with an oxygen
diffusion barrier.
14
/Burner Alternatives
(continued)
Burner manufacturer
Weishaupt or Riello
Burner/Gas train approval
Standard approvals are CSA (for Canada)
and UL (for U.S.). IRI and FM approved
equipment is also available - please inquire.

Electrical requirements

Weishaupt W Series burners are available in
120 VAC, single-phase, in a 60 Hz
configuration. L, G, and GL Series burners
listed below are available in 120 VAC single
phase, 208 VAC three-phase, 460 VAC
three-phase, or 575 VAC three-phase, all in
60 Hz configuration. It is generally
acceptable to use voltages within ten
percent of the supply voltage. Available
voltage inside boiler room must be provided
at time of order. Ensure appropriate
disconnect means and overcurrent
protection.
Natural gas pressure
Natural gas pressures and heating values as
provided by the gas utilities vary greatly
across North America. Select the
appropriate gas train accordingly. Low
pressure gas trains have a maximum input
of 14 "w.c.; high pressure gas trains have a
maximum pressure of 5 psig. Minimum gas
pressures apply - please inquire. Gas
pressures and heating values at site must be
provided at time of order.
Factory prewired components
Custom factory prewiring by Viessmann
ensures optimal functionality, compliance
with regional requirements, and ease of
installation in the field. Pricing provided by
Viessmann includes all necessary hardware
items such as junction panel, burner power
supply, boiler door safety switch (where
necessary), and all essential pressure
switches, as well as interconnection with
conduit between control and burner.
Electrical drawings provided upon product
delivery.
Boiler/Burner start-up
Vitorond 200, VD2 boilers with Weishaupt
burners require start-up by Viessmann.
Please inquire to obtain details regarding the
necessary prerequisites of boiler/burner
start-up procedures.
IMPORTANT
To minimize delivery lead times, please
ensure that critical technical information is
provided at time of order. Viessmann will
not process an order without site-specific
information regarding available voltage and
gas pressure. In addition Viessmann
recommends that gas pressure information
be provided in writing by the local gas
utility.
VITOROND 200, VD2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vd2-125Vd2-160Vd2-195Vd2-230Vd2-270

Table of Contents