Viessmann VITOROND 200 Technical Data Manual

Oil-/gas-fired boiler, triple-pass hot water heating boiler 490 to 1096 mbh / 144 to 321 kw
Hide thumbs Also See for VITOROND 200:

Advertisement

VITOROND 200
Triple-pass hot water heating boiler
490 to 1096 MBH / 144 to 321 kW
Technical Data Manual
Model Nos. and pricing: see Price List
Product may not be exactly as illustrated.
Vitorond 200
Oil-/Gas-fired boiler
sectional cast iron design
with Eutectoplex heat transfer surface, in triple-pass design
for operation with modulating water temperatures
Heating input: 490 to 1096 MBH
144 to 321 kW
5285 661 v1.4 01/2008

Advertisement

Table of Contents
loading

Summary of Contents for Viessmann VITOROND 200

  • Page 1 VITOROND 200 Triple-pass hot water heating boiler 490 to 1096 MBH / 144 to 321 kW Technical Data Manual Model Nos. and pricing: see Price List Product may not be exactly as illustrated. Vitorond 200 Oil-/Gas-fired boiler sectional cast iron design...
  • Page 2: Product Information

    Product Information VITOROND 200 The modular sectional cast iron design of the Vitorond 200, VD2 allows for problem-free transport into difficult-to-access boiler rooms and permits easy assembly. The triple-pass design ensures clean, low-emission combustion, while the Eutectoplex heat exchanger surface...
  • Page 3 4” / 100 mm thick pass intelligent and easy to install, insulation insulation operate and service. Second Combustion Eutectoplex heat exchanger Low-emission pass chamber surface constructed from burner homogeneous special gray cast iron Product may not be exactly as illustrated. VITOROND 200, VD2...
  • Page 4: Technical Data

    Cast iron heat exchanger block 1347 1556 1750 1940 2052 Overall weight complete with insulation 1424 1624 1845 2044 2196 Boiler water content 20.6 24.0 27.5 30.9 34.3 Max. boiler temperature °F (= fixed high limit) °C VITOROND 200, VD2...
  • Page 5 Vent pipe collar diameter does not automatically indicate vent/chimney size. See page 13 for details. The combustion burner head material must be suitable for temperatures of at least 932 °F / 500 °C. " For information regarding other Viessmann System Technology componentry, please reference documentation of respective product. " VITOROND 200, VD2...
  • Page 6 5½” / 140 mm Width 4” / 100 mm Total width Attention Viessmann North America offers the side-mounted control option only. Refer to the side-mounted control dimension on page 4. Burner Installation The burner must be fitted to the burner plate;...
  • Page 7 H 1 3-Way return water mixing valve, Selection of the correct package depends on 1 actuator, 1 circulating pump the characteristics of the heating system, and the degree of control necessary to protect the boiler. Contact Viessmann for assistance. VITOROND 200, VD2...
  • Page 8 100% Boiler Flow Package to verify that all pumps in the system operate correctly. The responsibility for the distribution system design, including all circulation pumps, remains with the system designer. Boiler return connection Boiler return header VITOROND 200, VD2...
  • Page 9 9” / 229 mm Flue (gas) 6” / 150 mm Front 6” / 150 mm Floor non-combustible IMPORTANT Maintain 1” air clearance from uninsulated hot water pipes to combustible material. IMPORTANT Boiler must not be installed on carpet. VITOROND 200, VD2...
  • Page 10 Waterside Flow mbar ”W.C. 1000 The Vitorond 200 boiler is designed for closed loop, forced circulation, hot water heating systems only. The recommended water flow rate through the Vitorond 200 is based on a temperature difference of between 20°F and 40°F / 11°C and 22°C (see table below).
  • Page 11: Operational Details

    - Gas-fired 149°F / 65°C - min. return water temperature 127°F / 53°C Setback operation Minimum boiler water temperature: The Viessmann control included in the - Oil-fired 122°F / 50°C standard equipment - Gas-fired 140°F / 60°C For multiple-boiler installations:...
  • Page 12: Standard Equipment

    Please inquire. Limited application only. Please inquire. The control of the Vitorond 200, VD2 boiler can be mounted either on the left- or right-hand side of the boiler. Please specify control location at the time of order. VITOROND 200, VD2...
  • Page 13: System Design Considerations

    For oil-fired boilers, use the “Installation Code for Oil For #2 fuel oil applications, use a The Vitorond 200, VD2 boiler is approved Burning Equipment CAN/CSA-B139” single-acting type. as a Category I appliance and must be (Canada), or NFPA 31 (USA).
  • Page 14: Water Quality

    208 VAC three-phase, 460 VAC systems. System also may contain Vitorond 200, VD2 boilers with Weishaupt three-phase, or 575 VAC three-phase, all in components which might be negatively burners require start-up by Viessmann.
  • Page 15 2-stage with assembled gas train Natural gas-fired Model n.a. RS28/M fully modulating Propane gas-fired Model n.a. RS28/M fully modulating Combination Model n.a. RLS28/M 2-stage NG, 2-stage oil Natural gas-fired Model n.a. RS45/M LN fully modulating low NO VITOROND 200, VD2...
  • Page 16 Viessmann Manufacturing Company (U.S.) Inc. Viessmann Manufacturing Company Inc. 45 Access Road 750 McMurray Road Warwick, Rhode Island • 02886 • USA Waterloo, Ontario • N2V 2G5 • Canada Tel. (401) 732-0667 • Fax (401) 732-0590 Tel. (519) 885-6300 • Fax (519) 885-0887 www.viessmann-us.com •...