Control units
(cont.)

Extension EA1

Part no. 7452 091
Function extension inside the casing for wall mounting.
Using the inputs and outputs allows up to 5 functions to be ach-
ieved:
1 switching output (floating changeover contact)
■ Central fault message issue (only with the Vitotronic 100, type HC1B
and Vitotronic 200, type HO1B)
■ Switching a feed pump to a substation
■ Switching the DHW circulation pump (only with the Vitotronic 200,
type HO1B)
1 analogue input (0 to 10 V)
■ Set boiler water temperature default
3 digital inputs
■ External heating program changeover for 1 to 3 heating circuits (only
with the Vitotronic 200, type HO1B, and the Vitotronic 300-K,
type MW2B)
■ External blocking
■ External blocking with central fault message
■ Minimum boiler water temperature demand
■ Fault messages
■ Short term operation DHW circulation pump (only with the
Vitotronic 200, type HO1B, and Vitotronic 300-K, type MW2B)
■ Signalling reduced operation for one heating circuit (only for the
Vitotronic 300-K, type MW2B)
0
1 8
5 8
Appendix
6.1 Regulations / Directives

Regulations and Directives

The design and operational characteristics of the Vitodens gas con-
densing boilers from Viessmann meet the requirements of EN 297.
They are CE-designated.
They may be installed in sealed unvented heating systems with per-
missible flow temperatures (= safety temperatures) up to 100 ºC to
EN 12828. The maximum achievable flow temperature is approx.
15 K below the safety temperature.
Observe all standards and guidelines applicable to the installation and
operation of this system in your country.
Only qualified contractors must carry out the installation, the mains gas
and flue gas connections, the commissioning, the electrical connection
as well as general maintenance and repair work.
The installation of a condensing boiler may need to be notified to and
approved by your local gas supply utility.
VITODENS 200-W
Specification
Rated voltage
Rated frequency
Rated current
Power consumption
Rated breaking capacity of the relay
output
Safety category
IP rating
Permissible ambient temperature
– during operation
– during storage and transport
In some regions, permits may be required for the flue system and con-
densate drain into the public sewage system.
In some countries, the relevant flue gas inspector and water authorities
must be informed prior to commencing the installation.
We recommend that you carry out maintenance and cleaning proce-
dures annually. As part of the maintenance procedure, check the cor-
rect function of the entire system. Remedy any faults.
Condensing boilers must only be operated with specially designed,
tested and approved flue pipes.
Only recognised contractors may convert this boiler for use in countries
other than those stated on the type plate. That contractor must also
arrange approval in accordance with the statutes of that country.
230 V~
50 Hz
2 A
4 W
2(1) A 250 V~
I
IP 20 D to EN 60529
ensure through appropriate
design/installation
0 to +40°C
Installation in living spaces or
boiler rooms
(standard ambient conditions)
–20 to +65 °C