Set Up and Calibration Procedures
Calibration
Step
Operation
Calibrate Zero (0%)
2
Calibrate Span
3
(100%)
4
Slidewire Emulation
The HercuLine
do a calibrationin the field, adjust the output using the procedure in Table 28. Refer to Figure 26 for a
diagram to connect a signal source to the actuator input and a DVM to measure actuator output signal.
ATTENTION
For a slidewire emulation output calibration to be saved, you must complete the procedure.
The calibration will not be saved if you exit without completing the steps of the procedure.
To exit calibration mode, press DISPLAY or SETUP keys.
72
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
Press
FUNCTION
or
key
FUNCTION
or
key
FUNCTION
®
2001/2002 Actuator comes already calibrated from the factory. If it becomes necessary to
Upper Display =
Lower Display =
Read meter connected to actuator output.
Adjust actuator output to a value equal to 0% output as read
from the DVM.
NOTE: Typically for a 4 mA output, the display will show a value
of approximately 382. A lower limit value is imposed on the zero
output. If the value is 357 or lower, the actuator will not allow you
to calibrate the zero output. The value must be larger than 357
for a valid calibration.
Upper Display =
Lower Display =
Read meter connected to actuator output.
Adjust actuator output to a value equal to 100% output as read
from the DVM.
NOTE: Typically for a 20 mA output, the display will show a
value of approximately 1887.
Calibration for zero and span output values are now stored.
Output calibration is complete.
Result
xxx
ZERO
xxxx
SPAN
Revision 7
7/08