Communications
Operating Temperature
Position sensing
Sensitivity
Hysteresis
Deadband
Repeatability
Repositions
(minimum @ 90 or 150
degree stroke)
Table 1 option –050-
Table 1 option –100-
Table 1 option –200-
Table 1 option –400-
Table 1 option –600-
Voltage/ Supply
Stability
Temperature
Coefficient
Zero Suppression
Input Filters
Solid State Motor
Control
Failsafe operation
Direction of Rotation
Duty Cycle
Revision 7
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
7/08
®
HercuLine
2002
Slidewire emulation - Provides
output voltage ratiometric to
shaft position and
potentiometric to supply voltage
(1 Vdc to 18 Vdc) without a
slidewire. Emulates a 100 ohm
to 1000 ohm slidewire. 10 mA
output maximum.
Modbus RTU or optional HART™
–40°C to +75 °C (–40°F to +170 °F)
Non-contact position sensor
0.2 % to 5 % of 90° span, proportional to deadband
Less than 0.4 % of full scale
0.2 % to 5 % of 90° span, programmable. Shipped at 0.5 %
0.2 % of 90° span
160
290
450
700
900
0.25 % of span with +10/–15 % voltage change
Less than ± 0.030 % of span per degree C for 0 °C to 50 °C
Less than ± 0.05 % of span per degree C for –40 °C to 75 °C
90 % of span.
Selectable spike and low pass filters.
Two triac switches for clockwise or anti-clockwise motor operation.
Transient voltage protection provided.
If input signal exceeds configured input range. Selectable and
adjustable.
Field programmable
Continuous
Technical and Operating Specifications
®
HercuLine
2001
1000 ohm film potentiometer
120
250
400
400
400
Specifications
®
HercuLine
2000/2003
NA
-40°C to +85 °C (-40°F to
+185 °F)
Dual 1000 ohm film
potentiometers
(not on 2003)
NA
NA
NA
NA
500
NA
NA
NA
NA
NA
NA
Wire swap