Set Up and Calibration Procedures
Relays Set Up Group
Relay Examples
Relay Type - Position Range
Selecting PosR relay type, you can cause the relay to energize when the actuator motor travels below 20%
of range and above 80% of range. Note in the example below that Relay 1 is set up to provide two trip
points. The first trip point (R11VAL) causes the relay to energize when the motor travels above 80%, the
second trip point (R12VAL) is set so the relay energizes when the motor travels below 20%.
The figure below shows the resulting action.
Motor
Position
46
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
Relay connector #1
Relay connector #2
Relay connector #3
Relay connector #4

Figure 22 Relay connectors

Set Up Group
SET RELAY1
0%
20%
17
18
Closed
Parameter
RTYP11
R11VAL
R11HL
RTYP12
R12VAL
R12HL
RLY1HY
80%
17
Open
Closed
RELAY 1
Normally Open
Value
PosR
80.0
HI
PosR
20.0
LO
0.0
100%
18
Revision 7
7/08