Siemens 2000592-001 User Manual page 64

Advance network communications board/datanet
Table of Contents

Advertisement

DataNET Troubleshooting Guiding,
Signal Quality
Problems
Placing Unit in Test Mode
54 • Troubleshooting
Continued
If the ANCB_DN port LED is never green, or intermittently flashes
between green and red, there may be a signal quality problem. Signal
levels should be examined to determine if a particular port has a signal
too large or too small relative to the other ports on the HUB. If a link fails
to connect at all, place the port in a test mode which will cause activity to
occur every ~50 milliseconds instead of every ~5 seconds as on an
unconnected link.
To place the unit in a test mode use the CLI commands to take the link
offline (port stop n) and initiate the test mode (test n). At this time, an
oscilloscope may be taken to the site of the slave device and connected
to monitor the signal. The signal received at the slave should be between
~0.75 v p-p and 5 v p-p. A signal smaller than ~0.75 v p-p is generally
not adequate. The impedance matching jumpers can be changed to
correct some signal level issues.
If the condition of excessive signal loss can not be corrected by jumper
settings, it may indicate inadequate cable properties (i.e. too long or
wrong type of cable).
The port can be taken off test mode and put back to normal operation
with the "test off" and "port start n" commands.