Controls And Adjustments; A) Default Dip Switch Settings; B) Harvest Timer (Dip Switch 1 & 2) - Hoshizaki KML-631MAH Service Manual

Low-profile modular crescent cuber
Hide thumbs Also See for KML-631MAH:
Table of Contents

Advertisement

3. Controls and Adjustments

a) Default Dip Switch Settings

The dip switch is factory-adjusted to the following positions:
Model
KML-631MAH
KML-631MWH
KML-631MRH
KML-631MAH
KML-631MWH
KML-631MRH
b) Harvest Timer (dip switch 1 & 2)
The harvest timer starts counting when the thermistor reads 48°F (9°C) at the evaporator
outlet.
No adjustment is required under normal use, as the harvest timer is adjusted to the
suitable position. However, a setting longer than the factory setting may be advised in
cases where the flush provided at harvest needs to be prolonged for extra cleaning.
Before changing this setting, call the HOSHIZAKI Technical Support Department at
1-800-233-1940 for recommendations. Keep in mind that setting the harvest timer to a
longer setting will decrease 24 hour production.
Auxiliary
Code
1
2
S-0, S-2
ON ON OFF OFF ON
T-0 and later ON OFF OFF OFF ON
Freeze Timer (9 & 10)
Normally in the off position.
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
Dip Switch Setting
No. 1
No. 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Dip Switch No.
3
4
5
6
7
ON OFF OFF OFF ON
ON OFF OFF OFF ON
Time
(seconds)
60
90
120
180
20
8
9
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kml-631mwhKml-631mrh

Table of Contents