Honeywell Q7300H System Integration Manual page 37

Communicating subbase system integration user address manual
Hide thumbs Also See for Q7300H:

Advertisement

Q7300H COMMUNICATING SUBBASE SYSTEM INTEGRATION USER ADDRESS MANUAL
User Address
T7300CommFailed
Communications between the T7300 Thermostat and the Q7300 subbase has failed.
All User Addresses starting with a g are identical in purpose to the UserAddresses of the same name but
gStatusBypTimer
without the g . The g points exist for binding to other nodes (they use the Guaranteed Periodic Update
mechanism), while the non-g points are used for polling from a monitoring tool or workstation.
gStatusCmdMode
gStatusCoolStgsOn
gStatusDlcShed
gStatusDuctTemp
gStatusEconOn
StatusOvrd
Effective manual override state arbitrated from OverridePriority, DestManOcc, DestBypass,
StatusLocalOvrRide and StatusBypTimer. Valid values are:
StatusRmTemp
StatusRmTemp is the room temperature used to control the temperature of the room. If DestRmTemp is
invalid, then the local and/or remote sensor (as selected by TempSensor) is reported in StatusRmTemp and
SrcRmTemp. If DestRmTemp is not invalid, then DestRmTemp is reported in StatusRmTemp and
SrcRmTemp. If DestRmTemp is invalid and the local and/or remote sensor (as selected by TempSensor) is
also invalid (because of sensor failure), then StatusRmTemp and SrcRmTemp are also invalid and room
temperature can no longer be controlled by this node.
StatusRmTmpActSpt
Current temperature control point (i.e. the current actual space temperature setpoint that the node is trying to
maintain in the conditioned space) is reported in StatusRmTmpActSpt and SrcRmTempActSpt.
SrcRmTempActSpt is updated from StatusRmTmpActSpt according to the SGPU mechanism where a
significant change is plus or minus 0.07 degrees C.
StatusSysFanCmd
Indicates the status of the thermostat fan switch. On
the Auto position.
Table A3. Status Points (Right Continued).


Occ
Effective manual override is occupied.

UnOcc
Effective manual override is not occupied.

Bypass
Bypass Timer is running in this node or another node and effective manual override is occupied.
Standby

Effective manual override is Standby.
Null
No manual override of the schedule occupancy.
Comments

Fan switch is in the On position. Off
37

Fan switch is in
(continued)