Download Print this page

Honeywell Q7300H System Integration Manual page 13

Communicating subbase system integration user address manual
Hide thumbs Also See for Q7300H:

Advertisement

Q7300H COMMUNICATING SUBBASE SYSTEM INTEGRATION USER ADDRESS MANUAL
User Address
tAuto
User Mode Switch–Auto setting.True= selected, False= not selected.
NOTE:
tBHeat
Equipment output relay
tBuildId
Thermostat software build identification string.
tcmBlockControl
Thermostat control algorithm. False = enabled; True = disabled.
tcmBlockEquip
Thermostat or subbase controls HVAC equipment via relay outputs. False = thermostat controls outputs; True
= thermostat blocked, subbase controls outputs.
tcmBlockSchedandUser
Thermostat user keys and thermostat time-of-day occupancy schedule enabled/disabled. False = enabled;
True = disabled.
tcmBlockSchedule
Thermostat time-of-day occupancy schedule. False = enabled; True = disabled.
tcmBlockUser
Thermostat user keys enabled. Some keys may be disabled by the thermostat installer setup.
tcmBlockUserAndDisplay
Thermostat user keys and display are enabled/disabled. False – enabled; True = disabled.
tcmResetWatchDog
Not used.
tcmUseNetSensor
Sensor used to control space temperature. False = use thermostat ensor(s); True = use network sensor via
communications subbase.
tCool
User Mode Switch–Cool setting. True = selected, False = not selected.
NOTE:
Table A1. Miscellaneous (Right Continued).
Only one User Mode Switch may be True at a time.

B. True = On; False = Off.
Only one User Mode Switch may be True at a time.
13
Comments
(continued)
63-4366

Advertisement

loading