Series 2000 Programmable Commercial

APPLICATION

The T7200, T7300 Thermostats and Q7300 Subbases control
24 Vac commercial single zone heating, ventilating and air
conditioning (HVAC) equipment. In addition, the Q7300H
Communicating Subbase can communicate schedule
information and system instructions to other devices in a
®
L
W
network.
ON
ORKS

FEATURES

All Models:
• 7-day programming.
• Two Occupied and two Unoccupied periods per day.
• Individual heat and cool setpoints available for
Occupied and Unoccupied periods.
• Proportional plus Integral (P+I) control eliminates
temperature fluctuations.
®
• Intelligent Recovery
control automatically optimizes
equipment start times based on building load.
• Intelligent Fan™ feature energizes fan continuously in
the Occupied periods. Fan can also be configured for
conventional heat or electric heat fan operation.
• Automatic or manual changeover models available.
• Universal Versaguard™ Thermostat guards available.
• Convenient overrides allow temporary setpoint
changes.
• Keypad lockout available.
® U.S. Registered Trademark
Copyright © 2001 Honeywell •
T7200D,E, T7300D,E,F and Q7300
Thermostats and Subbases
• All Rights Reserved
T7200D,E Thermostats:
• Use on single-stage conventional (T7200D) or heat
pump (T7200E) applications.
T7300D,E Thermostats:
• Use on multistage conventional (T7300D) or heat pump
(T7300E) applications.
• Models available with remote sensor capability.
T7300F Thermostats:
• Use on single-stage or multistage system in
conventional or heat pump applications.
• Auxiliary contacts on Q7300 can be used to interface
with C7400/W7459 Economizer System for total
integration of rooftop control.
• Remote temperature sensors available for use with
all models.
• Different levels of keypad lockout available.
Q7300 Subbase:
• Use with T7300D,E,F Thermostats.
• Auxiliary contacts can be used to interface with
C7400/W7459 Economizer System for total integration
of rooftop control.
• When used with the T7300F (revision 4 or later), the
Q7300H communicates with other network devices.
• Q7300L two stages of heat control ML7984 and V5011/
V5013 valve: stage 1 opens valve 40%; stage 2 100%.
• Q7300L provides two-speed fan control:
- Low: heat and occupied fan.
- High: cooling.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring Subbase/Wallplate ................................................
Settings ............................................................................
Installer Setup .................................................................. 10
Installer System Test ........................................................ 13
Programming .................................................................... 16
Operation .......................................................................... 19
General Operation Information ......................................... 21
Troubleshooting Guide ..................................................... 22
Cross Reference .............................................................. 23
Wiring Diagrams (Fig. 20-34) ........................................... 29
PRODUCT DATA
Contents
1
1
2
2
5
7
9
63-4355-4

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell T7200D

  • Page 1: Table Of Contents

    ® U.S. Registered Trademark Copyright © 2001 Honeywell • • All Rights Reserved Thermostats and Subbases T7200D,E Thermostats: • Use on single-stage conventional (T7200D) or heat pump (T7200E) applications. T7300D,E Thermostats: • Use on multistage conventional (T7300D) or heat pump (T7300E) applications.
  • Page 2: Specifications

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit might not exactly match the listed specifications. This product is tested and calibrated...
  • Page 3 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Electrical Ratings: 24 Vac, 50/60 Hz. 20 to 30 Vac, 50/60 Hz. Batteries: No batteries required. Auxiliary Heat and Emergency Heat Indication: Thermostat display indicates when Auxiliary Heat or Emergency Heat are activated.
  • Page 4 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Occupied Program Start Time Temporary Set Current Occupied Day/Time Continous Unoccupied M16292 1 T7200 WALLPLATE DOES NOT HAVE THE LED EXTENSION Fig. 1. Dimensions of T7200, T7300 and Q7300 in in. (mm).
  • Page 5: Installation

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES INSTALLATION When Installing this Product… 1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
  • Page 6 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES SUBBASE T7047C T7047G T7047C Fig. 5. Two T7047C Sensors and one T7047G Sensor providing temperature averaging network for T7300/Q7300 Thermostat/Subbase. SUBBASE T7047C T7047C T7047C T7047C Fig. 6. Four T7047C Sensors providing temperature averaging network for T7300/Q7300 Thermostat/Subbase.
  • Page 7: Wiring Subbase/Wallplate

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES WALL WIRES THROUGH WALL WALL ANCHORS LEDS Fig. 9. Mounting subbase or wallplate. Terminal Designations Standard Alternate Dry auxiliary contacts for economizer control; A1 is normally open during Unoccupied periods and closed during Occupied periods.
  • Page 8 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 6. Terminal Designations and Descriptions. (Continued) Terminal Designations Standard Alternate EB, EB — Q7300H L Fan relay. Cooling changeover valve. 24V system transformer. — 24V cooling transformer. —...
  • Page 9: Settings

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Mounting Thermostat on Subbase/Wallplate The thermostat mounts on the subbase/wallplate after it is installed: 1. Engage the tabs at the top of the thermostat and subbase/wallplate. See Fig. 11.
  • Page 10: Installer Setup

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES ENTER OCCUPIED PROGRAM MODE RETURNS TO NORMAL OPERATIONS Program SET OVERRIDE Temporary Occupied TEMPERATURE OFFSET AND ACTIVATE Continuous TEMPORARY Unoccupied OVERRIDE SET CURRENT ENTER HOLD MODE DAY AND TIME CLEAR PROGRAM PERIOD Fig.
  • Page 11 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES CAUTION Possible Equipment Damage. Fan must be running when system is operating. Heat pump and electric heat systems must be configured correctly in Installer Setup 2 to prevent equipment damage caused by the system running without the fan.
  • Page 12 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 7. Thermostat Installer Setup Options. (Continued) Installer Setup Number (Press Unoccupied Select Temp to change) Display Extended fan operation in heat (T7300F only). Extended fan operation in cooling (T7300F only).
  • Page 13: Installer System Test

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 7. Thermostat Installer Setup Options. (Continued) Installer Setup Number (Press Unoccupied Select Temp to change) Display Temperature display adjustment. Minimum off-time in heating. Not used. — Installer Setup...
  • Page 14: Thermostat Information

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Set Program Start Time Set Day/Time Em Ht Aux Ht Comm TueWedThuFriSatSun Occupied 12 Override Recovery System Em Heat Cool Auto Wait Fig. 15. LCD display of all segments.
  • Page 15 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Test Key to Press Number Heating Equipment System Test Heat/Cool Settings Emergency Heating Equipment System Test (T7300E,F with Q7300C,D) Heat/Cool Settings Cooling Equipment System Test Heat/Cool Settings Fan Equipment System Test...
  • Page 16: Programming

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Setting Keypad Lockout Switch (T7300 only) The DIP switch 1, on the thermostat back, activates the lockout features. The switch must be set ON (up) to activate the lockout feature (see Fig. 17).
  • Page 17: Copying A Day

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Setting Program Times 1. Press Occupied Start Time. NOTE: Anytime a start time is not required, press Clear Start Time. Set Program Occupied Start Time Set Program Set Temperature...
  • Page 18 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Setting Program Temperature Setpoints NOTE: The setpoint temperature range is 40°F to 90°F (7°C to 31°C) for heating and 45°F to 99°F (9°C to 37°C) for cooling. 1. Press Occupied Temp.
  • Page 19: Operation

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES 3. Press increase or decrease temperature offset is displayed (range is 0°F to 5°F). Set Program Set Temperature Change Time/Temp Occupied Unoccupied Occupied Unoccupied Program Start Time Start Time...
  • Page 20 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES T7200/T7300 and Conventional Thermostats P+I Control The T7200/T7300 microprocessor based control requires that the user understands temperature control and thermostat performance. A conventional electromechanical or electronic thermostat does not control temperature precisely at setpoint.
  • Page 21: General Operation Information

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Conventional System The T7200 and T7300D,F Thermostats with Q7300A,G,H Subbases are designed for conventional heat/cool applications. Heat Pump Operation The T7200E and T7300E,F Thermostats with Q7300C,D,H Subbases are designed for heat pump applications. Additional information is required when configured for heat pump applications.
  • Page 22: Troubleshooting Guide

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES (HOT) Q7300 SUBBASE AUXILIARY RELAY CONTACTS POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. RELAY REQUIRED (R8222 OR SIMILAR). Fig. 19. Use of external relay and transformer for auxiliary loads greater than 1.6A.
  • Page 23: Cross Reference

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 13. Troubleshooting Information. (Continued) Symptom Temperature settings Trying to set heat and cooling setpoints change from original too close together. Automatic changeover setting. thermostat models have a deadband.
  • Page 24 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 14. Differences from existing T7300/Q7300 to new T7300/Q7300 Series 2000 devices. Feature/Function Present T7300/Q7300, T8611, T8621 Families System switching Mechanical switch on Q7300 subbase. Fan switching Mechanical switch on Q7300 subbase.
  • Page 25 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 15. Thermostat and Subbase Cross Reference. (Continued) Model Number Description Q7300C1105 2-stage heat pump with auxiliary heat (3H/2C); gray color. T7300F2010/Q7300C2012 Wiring differences (old=new): B=A3. Q7300D Multistage heat pump subbase; does not include O or B terminals; system switch: AUTO-COOL-OFF-HEAT-EM HEAT; fan switch: AUTO-ON.
  • Page 26 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 15. Thermostat and Subbase Cross Reference. (Continued) Model Number Description T7300A1005 Honeywell logo. T7300A1013 York logo; part no. 025-27506. T7300A1021 Lennox logo; part no. 81G5901. T7300A1039 Trane logo; part no. THT-0608.
  • Page 27 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 15. Thermostat and Subbase Cross Reference. (Continued) Model Number Description T8621B7000 Carrier logo; LOW and HIGH SPEED LED; used on multispeed equipment; part no. HH07AX011. T8621B7018 BDP multi-logo; LOW and HIGH SPEED LED; used on multispeed equipment;...
  • Page 28 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 15. Thermostat and Subbase Cross Reference. (Continued) Model Number Description Y7300A1000 Contains one T7300A1047 Thermostat and one Q7300A1059 Subbase; Micrometl part no. 1060A-100. Y7300A1018 Contains one T7300A1062 Thermostat and one Q7300F1041 Subbase;...
  • Page 29: Wiring Diagrams (Fig. 20-34)

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 16. T7300/Q7300 Series 2000 Cross Reference. (Continued) Figure Model Number Number T7200D2008 Honeywell logo; no system or fan settings. T7200E One-stage heat and one-stage cool heat pump thermostat.
  • Page 30 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES COMPRESSOR CONTACTOR (HOT) COOLING TRANSFORMER POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER.
  • Page 31 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES DISCHARGE SENSOR COMPRESSOR EM. HT. CONTACTOR 1 RELAY COOL CHANGEOVER VALVE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS. USE A1 AND A2 WHEN THE CONTACT SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE.
  • Page 32 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES COMPRESSOR MODE CONTACTOR 2 EM. HT. COMPRESSOR RELAY CONTACTOR 1 COOL CHANGEOVER VALVE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. EM. MODE IS ON CONTINUOUSLY IN EMERGENCY HEAT MODE.
  • Page 33 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES COMPRESSOR COMPRESSOR CONTACTOR 1 DISCHARGE CONTACTOR 2 SENSOR COMPRESSOR RELAY CONTACTOR 3 (HOT) COOLING TRANSFORMER POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER.
  • Page 34 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES COMPRESSOR DISCHARGE CONTACTOR 2 SENSOR COMPRESSOR CONTACTOR 1 COOL CHANGEOVER VALVE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS. USE A1 AND A2 WHEN CONTACTS ARE NORMALLY CLOSED IN OCCUPIED MODE.
  • Page 35 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES HIGH SPEED DISCHARGE RELAY SENSOR COOLING SPEED RELAY RELAY (HOT) FAN TRANSFORMER POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONNECT GND TO EARTH GROUND. SEE TABLE 2 FOR VALVE AND VALVE ACTUATOR MODELS.
  • Page 36 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES ML7984 VALVE ACTUATOR DISCHARGE SENSOR (HOT) TRANSFORMER POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. INDEPENDENT FAN TRANSFORMER IS OPTIONAL. JUMPER FC TO R WHEN SINGLE TRANSFORMER IS USED.

Table of Contents