Panasonic MEW01349 Operating Instructions Manual page 69

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
Connected equipment might be "missing".
End-of-line resistor(s) missing or not correct value, 1-5
resistors (33K).
NOTE! The calibrated value has to be in the range 4K7-50K.
FAULT: Supervised output x,
technical number xxxxxx
This fault message is valid for a COM loop output unit 3364 output.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED Fault / Disablements "Alarm devices" (L11)
blinking.
If the output is programmed for fire brigade tx (type Routing
equipment), it is also indicated by LED Fault / Disablements "Fire
brigade tx" (L12) blinking.
Calibration not performed via menu H5/A1.
Short-circuit / break on the connected cable / equipment.
Connected equipment might be "stolen".
End-of-line capacitor(s) missing or not correct value, 1-5
capacitors (470 nF).
NOTE! The calibrated value has to be in the range 470 nF – 5 x
470 nF (2350 nF).
FAULT: Temperature sensor control unit xx
The sensor is not correctly connected or is missing.
FAULT: TLON-board 1590 (Network 0),
control unit xx
FAULT: TLON-board 1590 (Network 1),
control unit xx
TLON connection board 1590.
No communication / connection with the TLON network. The board
for Network 0 or 1 in control unit no. xx has to be replaced.
FAULT: Wrong type expansion board x
loop x control unit xx
This is valid for the I/O Matrix board 4582 no. x connected on COM
loop x in the control unit no. xx.
Check the board type, set with jumpers JP4 and JP5 on the I/O Matrix
board. The type should be the same as programmed via WinG3.
67

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl512 g3 v1.1.x

Table of Contents