Operating Instructions Fire alarm system EBL512 G3, V1.1.x
001 002 003 004
(
NOTE! See chapter "The information area priority
order", page 22 regarding priority order.)
Zones in test mode:
001 002 003 004
Please wait....
H7 Perform ZONE TEST
NOTE_1! During the test, the following information will be shown in
all other c.i.e. displays:
Zones in test mode: 001, 002, 003, 004
NOTE_2! If an alarm point (e.g. a manual call point) is in alarm state
when the test mode is ended, there will not be a fire alarm activated.
Instead the alarm point will be disabled and has to be re-enabled again
via menu H2/B5.
NOTE_3! When the "Fire door closing" function is used, the fire
door will be closed when the detectors controlling the door are tested,
in test mode.
End test: ↵
End test: ↵
128
H7 but still in test mode.
↲
Press "
" to end test.
The LED "Test mode"
(L8) is turned OFF.
If more zones are to be
tested, continue as above.
If not, scroll to another
menu or press "ESC".