Safe Shut Down Of Control Unit (H8/S6) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
31.7
Action
"Menu"
"↵ "
Scroll to menu S6.
"↲ "
"▼"
"↲ "
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Safe shut down of control unit (H8/S6)

It's not recommended to power off a control unit (i.e. no 230 V AC
and no battery) without first doing a safe shut down of control unit.
Safe shut down will save the SSW in a Flash ROM and put the CPUs
at rest. See also chapter "Restart", page 81.
It's recommended to do a safe shut down after commissioning the
installation and after the calibration of supervised outputs, change of
access code etc. in order to save the new valid values, codes etc.
Safe shut down can be performed from any control unit and any
control unit can be selected. A control unit without a front has to be
shut down from another control unit.
NOTE! By restart and power off, the Fault tx output(s) will be
"activated".
Text in display
S1 Disconnect loop / zone line input
S2 Re-connect loop / zone line input
S3 Acknowledge SERVICE signal
S4 Clear weekly average
S5 Test of alarm devices
S6 Safe shut down of control unit
S7 Activate address in alarm mode
S8 Synchronize the control units
S9 Change code for service / maintenance
S10 Change code for PC-communication
S6 Safe shut down of control unit
Shut down control unit 00?
Ready for shut-down, break the power.
Automatic restart within xxx seconds!
xxx will start at 300 seconds and countdown to 000 before
the control unit will restart automatically.
62
If not, a fault ("FAULT: Read/write site data (SSW), CU xx") might be
generated when you power up the control unit again.
No
Yes
137
62
Comments
Procedure according to
chapter "Access code for
service / maintenance (H5
and H8)", see page 116.
Write control unit number
and press "▼", i.e. select
"Yes".
The SSW is now saved and
the Main board and MMI
board CPUs are at rest.
You can now power off the
control unit.
If not, the control unit will
restart automatically after
5 minutes (300 seconds).