Operating Instructions Fire alarm system EBL512 G3, V1.1.x
Push buttons on the Fire Brigade Panel (FBP)
Operation/function
Used to silence the buzzer in the c.i.e.
Used to silence alarm devices / sounders (i.e. outputs of type
"Alarm devices" will be de-activated). Silenced Alarm
devices is indicated to the right in the display's soft key area
(a symbol near this button), see page 21.
Used to reset:
Fire alarms (see below)
Co-incidence alarms (if not automatically reset)
For more information see "Alarm reset", page 49.
NOTE! P3 has to be pressed for > 0.5 sec.
NOTE! This button exists in the Australian front only!
Disable zones in alarm.
The operation/function is shown above the key in the display
(i.e. the soft key area). The function of a soft key may vary
depending on the situation. If nothing is shown above the
key in the display, the key has no function for the moment.
Used when LEDs "Alarms queued" (L6) are lit, to
scroll/browse through the queued alarm points. Function, see
chapter "Fire alarm", page 39, under LEDs "Alarms
queued".
NOTE! Fire alarms are:
Fire alarm
Heavy smoke/heat alarm
Alert Annunciation (AA) alarm
Key cabinet alarm
Acknowledged alarm (New Zealand only)
Isolated alarm (New Zealand only)
2
The soft key "P7" has the function Evacuate in the following conventions:
Belgian, Brittish Standard, Hungarian, Spanish and Ukrainian. In all other
conventions it has the function Alert Annunciation Acknowledge.
18