After installation
is completed,
the following
method
must be used to
determine
if the exhaust
system is acceptable:
1. Connect
an inclined or digital
manometer
between
the dryer and the
point the exhaust
connects to the dryer.
2. Set the dryer timer and temperature
to air fluff (cool down)
and start the dryer.
3. Read the measurement
on the manometer.
The system back pressure must not be higher
than 0.75
inches
of water column,
If the system back pressure
is less than 0.75
inches of water column,
the system is acceptable.
Jf the
manometer
reading
is higher than 0,75
inches of water column,
the
system is too restrictive
and the installation
is unacceptable.
Although
vertical
orientation
of the exhaust
system is acceptable,
certain
extenuating
circumstances
could affect the performance
of the dryer:
1. Only the rigid metal duct work should
be used.
2, Venting vertically
through
a roof may expose
the exhaust
system to down drafts causing
an increase
in vent restriction.
3. Running
the exhaust system through
an area not insulated
may cause condensation
and faster accumulation
of lint.
4. Compression
or crimping
of the exhaust
system will
cause an increase
in vent restriction,
The exhaust
system should be inspected
and cleaned
a minimum
of every
18 months with normal
usage, The more the dryer is used, the more often
you should
check the exhaust system and vent hood for proper
operation,