The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
Clearance:
A: Mantel Height (min.)
B: Sidewall (on one side)
C: Ceiling
(room and/or alcove)
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
G: From Floor
Note:
F
HZ42 Regency Horizon
TM
Gas Fireplace

CLEARANCES

Dimension
Measured From:
13" (330mm)
Top of Fireplace Opening
8" (203mm)
Side of Fireplace Opening
22" (559mm)
Top of Fireplace Opening
13" (330mm)
22" Above Fireplace Opening
84" (2134mm)
Sidewall to Sidewall (Minimum)
36" (914mm)
Front to Back Wall (Maximum)
25-3/4"
Top of Fireplace Opening
0"
No hearth required
E
Alcove
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fi replace and vent
system be installed only in accordance with these instructions.
Flue Clearances to Combustibles
Horizontal - Top
Horiztonal - Side
Horiztonal - Bottom
Vertical
Passing through wall/
floor/ceiling - when
fi restop is used.
IMPORTANT NOTE
Combustible material can only be installed to
the bottom lip of the fi replace as shown below.
The fi nished fl oor must not come in contact with
the front face of the fi replace. Non-combustible
material (see "Framing and Finishing" section)
must act as a barrier between the front face and
fi nished fl oor.
INSTALLATION
3"
2"
2"
2"
1-1/2"