Circulating Air & Filters; Ductwork - Air Flow; Checking Duct Static - Goodman GKS9 Installation Instructions Manual

Gks9 series gas-fired warm air furnace
Hide thumbs Also See for GKS9:
Table of Contents

Advertisement

A gas detecting warning system is the only reliable way to detect a
propane gas leak. Rust can reduce the level of odorant in propane
gas. Do not rely on your sense of smell. Contact a local propane
gas supplier about installing a gas detecting warning system. If
the presence of gas is suspected, follow the instructions on Page
4 of this manual.
All propane gas equipment must conform to the safety standards
of the National Board of Fire Underwriters, NBFU Manual 58.
For satisfactory operation, propane gas pressure must be 11 inch
w.c. at the furnace manifold with all gas appliances in operation.
Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, depending on temperature of the liquid,
and "wetted surface" area of the container or containers.
2. Proper pressure regulation. (Two-stage regulation is
recommended for both cost and efficiency).
3. Pressure drop in lines between regulators, and between
second stage regulator and the appliance. Pipe size will
depend on length of pipe run and total load of all appliances.
Complete information regarding tank sizing for vaporization, rec-
ommended regulator settings, and pipe sizing is available from
most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead and most stan-
dard commercial compounds, special pipe dope must be used.
Shellac-based compounds resistant to the actions of liquefied pe-
troleum gases such as Gasolac
Crane
®
are satisfactory.
Refer to the following illustration for typical propane gas installa-
tions.
First Stage
Regulator
200 PSIG
Maximum
Propane Gas Installation (Typ.)
Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Tubing Size, O.D. Type L
Length,
3/8"
1/2"
Feet
10
730
1,700
20
500
1,100
30
400
920
40
370
850
50
330
770
60
300
700
80
260
610
100
220
540
125
200
490
150
190
430
175
170
400
200
160
380
To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879
Propane Gas Piping Chart I
®
, Stalactic
®
, Clyde's
5 to 15 PSIG
(20 PSIG Max.)
Continuous
11" W.C.
Second Stage
Regulator
Nominal Pipe Size
Schedule 40
5/8"
3/4"
7/8"
1/2"
3,200
5,300
8,300
3,200
2,200
3,700
5,800
2,200
2,000
2,900
4,700
1,800
1,700
2,700
4,100
1,600
1,500
2,400
3,700
1,500
1,300
2,200
3,300
1,300
1,200
1,900
2,900
1,200
1,000
1,700
2,600
1,000
900
1,400
2,300
900
830
1,300
2,100
830
780
1,200
1,900
770
730
1,100
1,800
720
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Length,
3/8"
Feet
10
39
20
26
30
21
40
19
50
18
60
16
80
13
100
11
125
10
150
9
200
8
250
8
*Data in accordance with NFPA pamphlet NO. 54
D
- A
UCTWORK
Duct systems and register sizes must be properly designed for the
CFM and external static pressure rating of the furnace. Design the
ductwork in accordance with the recommended methods of "Air
Conditioning Contractors of America" Manual D.
Install the duct system in accordance with Standards of the Na-
®
or John
tional Board of Fire Underwriters for the Installation of Air Condi-
tioning, Warm Air Heating and Ventilating Systems. Pamphlets No.
90A and 90B.
A closed return duct system must be used, with the return duct
connected to the furnace. NOTE: Ductwork must never be attached
to the back of the furnace. Flexible joints may be used for supply
and return connections to reduce noise transmission. To prevent
the blower from interfering with combustion air or draft when a
central return is used, a connecting duct must be installed be-
tween the unit and the utility room wall. Never use a room, closet,
or alcove as a return air chamber.
NOTE: Two side openings or a side opening and bottom opening
are required for airflow delivery of 1800 CFM and greater.
C
D
HECKING
UCT
Refer to your furnace rating plate for the maximum ESP (external
duct static) rating.
Total external static refers to everything external to the furnace cabi-
net. Cooling coils, filters, ducts, grilles, registers must all be con-
sidered when reading your total external static pressure. The sup-
3/4"
ply duct pressure must be read between the furnace and the cool-
ing coil. This reading is usually taken by removing the "A" shaped
7,500
4,200
block off plate from the end on the coil; drilling a test hole in it and
4,000
reinstalling the block off plate. Take a duct static reading at the test
3,700
hole. Tape up the test hole after your test is complete. The negative
3,400
3,100
pressure must be read between the filter and the furnace blower.
2,600
Too much external static pressure will result in insufficient air that
2,300
2,100
can cause excessive temperature rise. This can cause limit switch
1,900
tripping and heat exchanger failure.
1,700
To determine total external duct static pressure, proceed as fol-
1,500
lows;
1. With clean filters in the furnace, use a draft gauge (inclined
manometer) to measure the static pressure of the return duct
at the inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct. (Positive Pres-
sure)
3. The difference between the two numbers is .4" w.c.
27
Tubing Size, O.D. Type L
1/2"
5/8"
3/4"
7/8"
1-1/8"
1/2"
92
199
329
501
935
275
62
131
216
346
630
189
50
107
181
277
500
152
41
90
145
233
427
129
37
79
131
198
376
114
35
72
121
187
340
103
29
62
104
155
289
89
26
55
90
138
255
78
24
48
81
122
224
69
21
43
72
109
202
63
19
39
66
100
187
54
17
36
60
93
172
48
Propane Gas Piping Chart II
XIII. CIRCULATING AIR & FILTERS
F
IR
LOW
S
TATIC
Nominal Pipe Size
Schedule 40
3/4"
1"
1-1/4" 1-1/2"
567
1,071
2,205
3,307
393
732
1,496
2,299
315
590
1,212
1,858
267
504
1,039
1,559
237
448
913
1,417
217
409
834
1,275
185
346
724
1,066
162
307
630
976
146
275
567
866
132
252
511
787
112
209
439
665
100
185
390
590