On Irect Ent Ingle Ipe Iping - Goodman GKS9 Installation Instructions Manual

Gks9 series gas-fired warm air furnace
Hide thumbs Also See for GKS9:
Table of Contents

Advertisement

E
DGES OF SHEET METAL HOLES MAY BE SHARP
PRECAUTION WHEN REMOVING HOLE PLUGS
A
V
/F
L
LTERNATE
ENT
LUE
OCATION
The alternate vent/flue location is the large hole directly in line with
the induced draft blower outlet. To use the alternate vent/flue loca-
tion refer to the following steps, the "Vent/Flue Pipe Cuts" figure,
and the "Alternate Vent/Flue Location" figure.
1. Remove and save the four screws securing the vent/flue
coupling to the furnace top panel.
2. Loosen the worm gear hose clamps on the rubber elbow
and detach it from both the induced draft blower and the
vent/flue pipe.
3. Remove the vent/flue pipe from the furnace.
4. Cut the vent/flue pipe 3.75 inches from the flanged end of
the pipe. See Vent/Flue Pipe Cuts figure. The section of
pipe attached to the coupling will reach through the side
panel to the induced draft blower. Discard remaining pipe
and elbows.
FLANGE
Vent/Flue Pipe Cuts
5. Remove plastic plug from alternate vent/flue location.
Relocate and install plug in standard vent/flue location (top
cover).
6. Insert cut section of vent/flue pipe and coupling into alternate
vent/flue location. Using a rubber coupling and worm gear
hose clamps from the drain kit bag, attach the vent/flue pipe
and coupling to the induced draft blower. Secure the
coupling to the cabinet using the screws removed in step 1
or with field-supplied 3/8" #8 self drilling screws.
T
HE RUBBER ELBOW IS NOT DESIGNED TO SUPPORT A LOAD
THE RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE
,
CABINET
EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT
-
/
FIELD
SUPPLIED VENT
FLUE PIPING
LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO
,
FLUE GASES
INCLUDING CARBON MONOXIDE
7. For upright installations, externally mount the rubber elbow
to the vent/flue coupling using a worm gear hose clamp.
Secure field supplied vent/flue piping to the rubber elbow
using a worm gear hose clamp. NOTE: Use of the alternate
vent/flue location for upright installations, requires the drain
trap be installed on the same side of the unit as the flue
pipe.
8. For horizontal installations, externally secure the field-
supplied vent/flue pipe directly to the vent/flue coupling using
a PVC or ABS coupling or elbow.
WARNING
. U
SE GLOVES AS A
.
3.75"
CUT HERE
WARNING
,
AS DAMAGE CAN RESULT IN
.
SECURE TO
ID BLOWER WITH
RUBBER COUPLING
AND HOSE
CLAMPS
N
-D
V
ON
IRECT
Non-direct vent installations require only a vent/flue pipe. The vent
pipe can be run horizontally with an exit through the side of the
building or run vertically with an exit through the roof of the building.
The vent can also be run through an existing unused chimney;
however, it must extend a minimum of 12 inches above the top of
the chimney. The space between the vent pipe and the chimney
must be closed with a weather-tight, corrosion-resistant flashing.
For details concerning connection of the vent/flue pipe to the fur-
nace, refer to Section IX, Vent/Flue Pipe and Combustion Air -
Standard Furnace Connections or Alternate Furnace Connections
for specific details. Refer to the following Non-Direct Vent (Single
Pipe) Piping - Vent/Flue Pipe Terminations for specific details on
termination construction.
Although non-direct vent installations do not require a combustion
air intake pipe, a minimum of one 90° elbow should be attached to
the furnace's combustion air intake if: an upright installation uses
. W
HEN
the standard intake location. This elbow will guard against inad-
vertent blockage of the air intake.
V
/F
P
ENT
LUE
IPE
Refer to the following table for applicable length, elbows, and pipe
diameter for construction of the vent/flue pipe system of a non-
direct vent installation. In addition to the vent/flue pipe, a single 90°
elbow should be secured to the combustion air intake to prevent
inadvertent blockage. The tee used in the vent/flue termination
must be included when determining the number of elbows in the
piping system.
15
3
REMOVE
PIPE
4 SCREWS
DETACH RUBBER
UPFLOW
6
CABINET WITH
UPFLOW/HORIZONTAL
Alternate Vent/Flue Location
(S
P
) P
ENT
INGLE
IPE
IPING
L
D
ENGTHS AND
IAMETERS
1
REMOVE
5
REMOVE
AND RELOCATE
2
ELBOW FROM
ID BLOWER AND
VENT/FLUE
PIPE
6
SECURE TO
SCREWS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents