Alternate Electrical And Gas Line Connections; Drain Pan; Freeze Protection; Furnace Suspension - Goodman GKS9 Installation Instructions Manual

Gks9 series gas-fired warm air furnace
Table of Contents

Advertisement

Recommended Installation Positions
NOTE: Alternate “vertical” piping connections can not be used when
an upflow furnace is installed with supply air discharging to the
right. In either case, use the standard flue and combustion air
piping connections.
A
E
G
L
C
LTERNATE
LECTRICAL AND
AS
INE
ONNECTIONS
This furnace has provisions allowing for electrical and gas line
connections through either side panel. In horizontal applications
the connections can be made either through the “top” or “bottom” of
the furnace.
D
P
RAIN
AN
A drain pan must be provided if the furnace is installed above a
conditioned area. The drain pan must cover the entire area under
the furnace (and air conditioning coil if applicable).
F
P
REEZE
ROTECTION
Refer to Section VII, Horizontal Applications and Conditions - Drain
Trap and Lines.
F
S
URNACE
USPENSION
If the furnace is installed in a crawl space it must be suspended
from the floor joist or supported by a concrete pad. Never install the
furnace on the ground or allow it to be exposed to water. Refer to
Section IV, Location Requirements and Considerations - Furnace
Suspension for further details.
VIII. PROPANE GAS /HIGH ALTITUDE INSTALLATIONS
WARNING
P
,
OSSIBLE PROPERTY DAMAGE
PERSONAL INJURY OR DEATH MAY
. T
OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED
HE
APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER
. A
FURNACE OPERATION
LL CONVERSIONS MUST BE PERFORMED BY
.
A QUALIFIED INSTALLER OR SERVICE AGENCY
This furnace is shipped from the factory configured for natural gas
at standard altitude. Propane gas installations require an orifice
change to compensate for the energy content difference between
natural and propane gas.
High altitude installations may require both a pressure switch and
an orifice change. These changes are necessary to compensate
for the natural reduction in the density of both the gas fuel and the
combustion air at higher altitude.
For installations above 7000 feet, please refer to your distributor
for required kit(s).
M anifold
Pre s s ure
Altitude
Gas
Kit
Orifice
Pre s s ure
Sw itch
Natural
None
#43
3.5" w .c.
0-7000
None
1
LPT-00*
Propane
#55
10.0" w .c.
2
LPT-03*
1
Supports White-Rodgers 1-stage valve only
2
Supports both Honeyw ell and White-Rodgers 1-stage valves
NOTE: In Canada, gas furnace s are ce rtifie d to 4500 fe e t.
Contact the distributor for a tabular listing of appropriate
manufacturer’s kits for propane gas and/or high altitude installa-
tions. The indicated kits must be used to insure safe and proper
furnace operation. All conversions must be performed by a quali-
fied installer, or service agency.
IX. VENT/FLUE PIPE & COMBUSTION AIR PIPE
G
ENERAL
WARNING
F
AILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY
. C
INJURY OR DEATH
AREFULLY READ AND FOLLOW ALL
.
INSTRUCTIONS GIVEN IN THIS SECTION
WARNING
U
,
PON COMPLETION OF THE FURNACE INSTALLATION
CAREFULLY
INSPECT THE ENTIRE FLUE SYSTEM BOTH INSIDE AND OUTSIDE OF
. L
THE FURNACE TO ASSURE IT IS PROPERLY SEALED
EAKS IN THE
FLUE SYSTEM CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH
,
DUE TO EXPOSURE TO FLUE PRODUCTS
INCLUDING CARBON
.
MONOXIDE
Page 12