On Irect Ent Ingle Ipe Iping - Goodman GMH95 Installation Instructions Manual

Gmh95/gch95/gme95/gch9 series gas-fired warm air furnace
Hide thumbs Also See for GMH95:
Table of Contents

Advertisement

1
3
REMOVE
REMOVE
4 SCREWS
PIPE
4
CUT PIPE PER
VENT/FLUE
PIPE CUTS
DIAGRAM
5
REMOVE
AND RELOCATE
2
DETACH RUBBER
ELBOW FROM
ID BLOWER AND
VENT/FLUE
PIPE
UPFLOW
COUNTERFLOW/UPRIGHT
(UPFLOW SIMILAR)
6
SECURE TO
ID BLOWER WITH
RUBBER COUPLING
AND HOSE
CLAMPS
UPFLOW/HORIZONTAL
(COUNTERFLOW SIMILAR)
Alternate Vent/Flue Location
N
-D
V
(S
ON
IRECT
ENT
INGLE
Non-direct vent installations require only a vent/flue pipe. The
vent pipe can be run horizontally with an exit through the side of
the building or run vertically with an exit through the roof of the
building. The vent can also be run through an existing unused
chimney; however, it must extend a minimum of 12 inches above
the top of the chimney. The space between the vent pipe and the
chimney must be closed with a weather-tight, corrosion-resistant
flashing. For details concerning connection of the vent/flue pipe
to the furnace, refer to Section IX, Vent/Flue Pipe and Combustion
Air - Standard Furnace Connections or Alternate Furnace Con-
nections for specific details. Refer to the following Non-Direct
Vent (Single Pipe) Piping - Vent/Flue Pipe Terminations for spe-
cific details on termination construction.
Although non-direct vent installations do not require a combus-
tion air intake pipe, a minimum of one 90° elbow should be at-
tached to the furnace's combustion air intake if: an upright instal-
lation uses the standard intake location. This elbow will guard
against inadvertent blockage of the air intake.
3
1.
REMOVE
REMOVE
PIPE
4 SCREWS
CUT PIPE PER
VENT/FLUE PIPE CUTS
DIAGRAM
REMOVE
3 SCREWS
REMOVE
AND RELOCATE
DETACH RUBBER
ELBOW FROM
ID BLOWER AND
VENT/FLUE
COUNTERFLOW
5
ADDITIONAL PLUG
FROM DRAIN KIT
7
EXTERNALLY
MOUNT
RUBBER ELBOW
6
SECURE TO
ID BLOWER WITH
RUBBER COUPLING
AND HOSE
CLAMPS
6
SECURE TO
CABINET WITH
SCREWS
P
) P
IPE
IPING
V
/F
P
ENT
LUE
Refer to the following table for applicable length, elbows, and
4
pipe diameter for construction of the vent/flue pipe system of a
non-direct vent installation. In addition to the vent/flue pipe, a
1
single 90° elbow should be secured to the combustion air intake
to prevent inadvertent blockage. The tee used in the vent/flue
5
termination must be included when determining the number of
elbows in the piping system.
2
Maximum Allowable Length of Vent/Flue Pipe (ft)
Models
PIPE
(kBtu_Tons)
040_3 or
045_3
060_3 or
070_3
GCH_090_4
GMH_090_4
080_5 or
090_5
100_5 or
115_5
1) One 90° elbow should be secured to the combustion air intake con-
nection.
2) Minimum requirement for each vent pipe is five (5) feet in length and
one elbow/tee.
3) Tees and/or elbows used in the vent/flue termination must be included
when determining the number of elbows in the piping system.
4) 2 1/2" or 3" diameter pipe can be used in place of 2" diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep
elbows should be considered equivalent to one 90 deg. elbow.
V
/F
P
ENT
LUE
NOTE: If either a 90 degree or 45 degree elbow is used for termi-
nation, it must be pointed downward.
The vent/flue pipe may terminate vertically, as through a roof, or
horizontally, as through an outside wall.
Vertical vent/flue pipe terminations should be as shown in the
following figure. Refer to Section IX, Vent/Flue Pipe and Com-
bustion Air Pipe - Termination Locations for details concerning
location restrictions. The penetration of the vent through the roof
must be sealed tight with proper flashing such as is used with a
plastic plumbing vent.
Horizontal vent/flue pipe terminations should be as shown in the
following figure. Refer to Section IX, Vent/Flue Pipe and Combus-
tion Air Pipe - Termination Locations for details concerning loca-
tion restrictions. A 2 3/8" diameter wall penetration is required for
2" diameter pipe. A 3" diameter hole is required for a 2 1/2" pipe
and a 3 1/2" diameter hole is required for 3" diameter pipe. To
secure the pipe passing through the wall and prohibit damage to
piping connections, a coupling should be installed on either side
of the wall and solvent cemented to a length of pipe connecting
the two couplings. The length of pipe should be the wall thick-
ness plus the depth of the socket fittings to be installed on the
inside and outside of the wall. The wall penetration should be
sealed with silicone caulking material.
In a basement installation, the vent/flue pipe can be run between
joist spaces. If the vent pipe must go below a joist and then up
into the last joist space to penetrate the header, two 45° elbows
should be used to reach the header rather than two 90° elbows.
17
L
D
IPE
ENGTHS AND
IAMETERS
Non-Direct Vent (Single Pipe)
Pipe
Number of Elbows
(4)
Size
(in.)
2
3
4
68
65
62
2 or 2 1/2
2 or 2 1/2
68
65
62
46
43
40
2 or 2 1/2
3
68
65
62
16
13
10
2 or 2 1/2
3
68
65
62
37
34
31
2 or 2 1/2
3
68
65
62
3
68
65
62
3
68
65
62
T
IPE
ERMINATIONS
(1 ) (2)
(3) (5 )
5
6
7
8
59
56
53
50
59
56
53
50
Not Recommended
59
56
53
50
Not Recommended
59
56
53
50
28
25
22
19
59
56
53
50
59
56
53
50
59
56
53
50

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents