PRODUCT DESIGN
Thermostats:
NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.
Filters:
Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or
CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty.
This furnace has provisions for the installation of return air filters at the side and/or bottom return. The furnace will
accommodate the following filter sizes depending on cabinet size:
Cabinet
Width
(in.)
Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in
the duct system such as a central return.
COOLING AIRFLOW REQUIREMENT (CFM)
600
800
0453BXA*
388*
388*
0703BXA*
---
647*
0704CXA*
---
0904CXA*
---
0905DXA*
---
1155DXA*
---
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter Area (in
[Based on a 300 ft/min filter face velocity]
10
Side Return(s)
Approx.
Nominal
Flow Area
Filter Size
(in.)
All
16 x 25 x 1
1000
1200
1400
1600
480
576
---
---
647*
647*
672
---
---
583*
583*
672
768
---
863*
863*
863*
863*
---
---
777*
777*
777*
---
---
971*
971*
971*
Upflow Filters
Bottom Return
Cabinet
Width
2
(in.)
(in
)
400
17-1/2
21
24-1/2
2000
0453BXA*
---
0703BXA*
---
0704CXA*
---
---
0904CXA*
0905DXA*
960
971*
1155DXA*
*Minimum filter area dictated by heating airflow requirement.
2
)
Permanent Minimum Filter Area (in
[Based on 600 ft/min filter face velocity]
Approx.
Nominal
Flow Area
Filter Size
2
(in.)
(in
)
14 x 25 x 1
350
16 x 25 x 1
400
20 x 25 x 1
500
COOLING AIRFLOW REQUIREMENT (CFM)
600
800
1000
1200
194*
194*
240
288
---
324*
324*
324*
---
---
291*
291*
---
---
432*
432*
---
---
---
388*
---
---
---
486*
1400
1600
2000
---
---
---
336
---
---
336
384
---
432*
432*
---
388*
388*
480
486*
486*
486*
2
)