RT-SVX20A-E4

Controls
Other accessories available
Remote temperature sensor to be
used with THS/THP 01-02.
TZS01: Remote room temperature
sensor to be used with THS/THP 03,
Tracker or Varitrac systems.
DTS: Duct temperature sensor to be
used with THS/THP 03.
TZS02: Remote room temperature
sensor with adjustable thumwheel
setpoint to be used with Tracker or
Varitrac systems.
TZS04: Room temperature sensor
with adjustable thumbwheel and
override button, to be used with
Tracker or Varitrac systems.
Refer to separate documentation for
more information.

Communication Interfaces

TRANE Communication Interface
(TCI-R) board
This is an electronic board, factory-
mounted in the main control panel,
needed to allow communication
between a TRANE Integrated
Comfort system (TRACKER or
Varitrac CCP2) and the unit. (COM3-
COM4)
LON Communication Interface
(LCI-R) board
This is an electronic board, factory-
mounted in the main control panel,
needed to allow communication on
a LonTalk
Network at the unit level.
®
LonTalk
®
Communication Interface
(LCI-R) board allows Voyager units
to communicate on a LonTalk
Network at the unit level. Network
variables are based on the
LonMark
®
. Space Comfort Controller
Functional Profile Template. The
LCIV uses a Free Topology
transceiver FTT-10A. The FTT-10A
transceiver supports non-polarity
sensitive, free topology wiring,
allowing the system installer to use
star, bus, and loop architecture. The
LCI-V can also be connected to an
optional High Temperature Limit
Switch if installed with the rooftop
unit. For more information, see
attached manual LTCI-IN-1.
®