Figure 25- Clogged filter sensor
1
1 = Secure with one screw
2 = Route wire harness between coil blockoff and roof rib
3 = Secure with pop-in wire tie
4 = Remove filter if necessary
RT-SVX20A-E4
Controls

Clogged filter detector

This device is mounted in the
indoor fan section. The sensor
measures the difference in pressure
before and after the filter section.
The information is sent to the THP03
thermostat, to a Tracker™ or to a
BMS. The setting range is 40 to
300 Pa.
2
3
4

Smoke detector

This device is used to detect smoke
in the air stream. It includes a
factory mounted detector connected
to a central panel, both fitted in the
fan section.
When smoke is detected, it shuts off
the unit. A dry contact is available
on the control panel for a remote
default.
High temperature safety
thermostat
This additional safety device is a
manual reset thermostat for gas
fired units (YKD/YKH), required
mainly by the French ERP
regulation. It is located in the gas
burner section. It stops the gas
burner and the supply air fan when
the supply air temperature rises to
120°C.

Remote fault relay

This is a factory mounted relay used
to send alarm signals (dry contact)
to a local BMS or a local control
panel. With this relay, the
compressor, heating, fan and power
supply alarm output signals from
the controller are reported to a
single dry contact.