Co 2 Sensors - Trane Voyager TSD/TSH 060 Installation And Operation Manual

Rooftop units
Table of Contents

Advertisement

Table 40 - Specifications
Measuring range CO
2
Accuracy at 25°C
Non-linearity
Temperature dependence of output
Long-term stability
Recommended calibration interval
Response time
Operating temperature
Storage temperature
Humidity range
Airflow range
Output signals (jumper selectable)
Resolution of analog outputs
Recommended external load
Power supply
Power consumption
Warm-up time
Dimensions (mm)
RT-SVX20A-E4
Controls
CO
sensors
2
Wall-mounted and duct-mounted
CO
sensors
2
Power supply requirements
CAUTION! Make sure that you
connect the power wire only to the
24V terminal. Connecting the power
wire to the output terminal may
result in equipment damage.
Wall-mounted
< +/- [40 ppm CO
+ 3% of
2
reading]
(included repeatability and
calibration uncertainty)
15-35°C
108 x 80 x 36
The CO
2
operate with a nominal 24 Vac
supply. The power supply should
maintain the voltage between 20 to
26 Vac.
Table 41 - CO
Wire size
(mm²)
0,25
0,5
1
0-2000 ppm
< 1.0% full scale
0.3% full scale/°C
< 5.0% full scale/ 5 years
5 years
1 minute (0-63%)
-20-70°C
0-85% relative humidity
0-10 Vdc
10 ppm CO
2
Current output: max 500
Voltage output: min. 1000
Nominal 24 Vac
< 5 VA
< 15 minutes
sensor is designed to
sensor wire size
2
Maximum
wire lengh
(m)
50
100
200
Duct-mounted
< +/- [30 ppm CO
+ 2% of
2
reading]
(included repeatability and
calibration uncertainty)
-5-45°C
0-10 m/s)
80 x 80 x 200
35