J. Assemble vent run to exterior wall - If not
previously measured, locate the center of the
vent at the exterior wall. Prepare an opening as
described in Step B. Assemble the vent system
to point where the terminus of the last section is
within 7
in. (191 mm) to 11
inboard of the exterior surface to which the
SV4.5HT termination is to be attached, see Fig-
ure 39 . If the terminus of the last section is not
within this distance, use the telescopic vent
section SV4.5LA, as the last vent section. For
wall thicknesses greater than that shown in
Figure 38 , refer to Table 3 on page 18 . This table
lists the additional venting components needed
(in addition to the termination and adapter) for a
particular range of wall thicknesses.
K. Attach termination adapter - Attach the
adapter (adapter - SV4.5RCH - provided with
the termination) to the vent section or tele-
scoping vent section), elbow or appliance col-
lar as shown in Figure 38 in the same manner
as any SV4.5 vent component (refer to Step E).
L. Install Firestop/Spacer at exterior wall -
When using the square termination, install
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)
Firestop/Spacer over the opening at the exte-
rior side of the framing, long side up, with the
3 inch spacer clearance at the top as shown in
Figure 38 , and nail into place.
(The Firestop/Spacer may also be installed over
the opening at the interior side of the framing.)
When using the round termination, a separate
firestop/spacer is not required since this ter-
mination has integral spacers which provide
the same function as a separate firestop/spacer.
M. Install the termination -
Install the square termination (SV4.5HT)- For
the last step , from outside the exterior wall,
slide the collars of the termination onto the
adapter until the termination seats against the
exterior wall surface to which it will be attached.
Orient the housing of the termination with the
arrow pointed upwards. Secure the termina-
tion to the exterior wall. The horizontal termi-
nation must not be recessed into the exterior
wall or siding by more than the 1 " (32 mm)
as shown in Figure 39 .
SFHRK Snorkel Cap –The snorkel cap is de-
signed to be fitted into a basement window box.
The SFHRK cap is for use with flex vent pipe.
Vertical distance between the inlet and outlet of
the cap is 28 in. (711 mm).
in. (298 mm)
6 to 48 inch Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Figure 38
*Cut termination collar for wall
thicknesses less than 7 in. (191 mm)
Siding
SV4.5HT
Square Termination
Stucco and Siding
Installation shown
Figure 39
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Firestop/Spacer (SV4.5HF) shown
on the exterior side of the wall. It
7"
(178)
12 "
(267 mm)
(308 mm)
5 "
(130 mm)
Adapter
SV4.5RCH
Note: Centerline of Vent Piping
is NOT the Same as the
Centerline of the Framed
Installing the Square Horizontal Termination (SV4.5HT)
Interior Surface of
Finished Wall
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
Last Vent Section. Use
Te l e s c o p i c
Section (SV4.5LA), If
Necessary
Stucco
Note - Firestop/Spacer (SV4.5HF)
required but not shown for clarity.
Venting Connection and Exterior Wall Recessing of the
Square Horizontal Termination (SV4.5HT)
may also be installed on the
interior side.
10 "
See Figure 9 (CDST), 10
Opening.
(CDPF), 11 (CDCL) or 12
(CDCR) on page 7 for Min.
Distance to Base of Appliance.
Base of Appliance
Minimum wall thickness
*5 in. (127 mm)
Maximum wall thickness
11 in. (298 mm)
Exterior Surface of Siding
Exterior Surface of
V e n t
Adapter
SV4.5RCH
*1 " Maximum Recess of
Square Termination into
Exterior Finishing Material
SV4.5HT
Termination
3"
(76 mm)
1"
(25.4 mm)
Framing
7 in. (191 mm) to
11 in. (298 mm)
SV4.5HT
Square
Termination
17