Bryant 581A Installation And Service Instructions Manual page 4

Single package rooftop electric cooling/gas heating units
Hide thumbs Also See for 581A:
Table of Contents

Advertisement

581A180 ONLY
Fig. 4 — Base Unit Dimensions; 581A155 and 180
ECONO-
STD UNIT
CORNER
MIZER
UNIT
WEIGHT
A
WEIGHT
581A
Lb
Kg
Lb
Kg
Lb
Kg
155
1725
782
110
50
427
194
180
1800
816
110
50
417
189
POWER EXHAUST/
BAROMETRIC RELIEF
(ACCESSORY ONLY)
CORNER
CORNER
CORNER
DIM A
B
C
D
Lb
Kg
Lb
Kg
Lb
Kg
ft-in.
390
177
438
199
470
213
3-3
399
181
481
218
503
228
3-2
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3.
Center of Gravity.
4.
Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
Rear: 7 ft-0 in. (2134) for coil removal. This dimension can be reduced
to 4 ft-0 in. (1219) if conditions permit coil removal from the top.
4 ft-0 in. (1219) to combustible surfaces, all four sides (includes between
units).
Left side: 4 ft-0 in.(1219) for proper condenser coil airflow.
Front: 4 ft-0 in. (1219) for control box access.
Right side: 4 ft-0 in. (1219) for proper operation of damper and power
exhaust if so equipped.
Top: 6 ft-0 in. (1829) to assure proper condenser fan operation.
Bottom: 14 in. (356) to combustible surfaces (when not using curb).
Control box side: 3 ft-0 in. (914) to ungrounded surfaces, non-combustible.
Control box side: 3 ft-6 in. (1067) to block or concrete walls, or other
grounded surfaces.
Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and the damper/
power exhaust as stated in Note no. 6, a removable fence or barricade
requires no clearance.
8. Dimensions are from outside of corner post. Allow 0 ft-
side for top cover drip edge.
POWER EXHAUST/
BAROMETRIC RELIEF
(ACCESSORY ONLY)
FIELD
SUPPLIED
DIM B
DIM C
mm
ft-in.
mm
ft-in.
mm
991
3-5
1051
1-10
559
961
3-6
1070
1-10
559
5
/
in. (8) on each
16