Table 7 — Fan Performance — 581A155300 (High Heat Units with Standard Indoor Fan Motor
CFM
0.2
Rpm
Watts
Bhp
3750
753
915
1.05
4000
764
1006
1.16
4250
798
1147
1.32
4500
832
1301
1.50
4750
868
1467
1.69
5000
903
1648
1.89
5250
939
1842
2.12
976
2050
2.36
5500
5750
1012
2273
2.61
1049
2511
2.89
6000
CFM
1.2
Rpm
Watts
Bhp
3750
1227
1973
2.27
4000
1241
2120
2.44
1258
2281
2.62
4250
4500
1275
2454
2.82
1295
2642
3.04
4750
5000
5250
5500
5750
6000
LEGEND
Bhp
— Brake Horsepower
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
*Standard low-medium static drive range is 834 to 1064 rpm. Alternate
high-static drive range is 1161 to 1426. Other rpms require a field-
supplied drive.
NOTES:
1. Maximum continuous bhp for the standard motor is 3.13. The maxi-
mum continuous watts is 2700. Do not adjust motor rpm such that
motor maximum bhp and/or watts is exceeded at the maximum
operating cfm.
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
Rpm
Watts
Bhp
844
1077
1.24
872
1211
1.39
901
1357
1.56
931
1516
1.74
962
1688
1.94
994
1873
2.15
1026
2073
2.38
1059
2286
2.63
1093
2514
2.89
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
Rpm
Watts
Bhp
1310
2218
2.55
1323
2368
2.72
1337
2531
2.91
0.6
Rpm
Watts
Bhp
Rpm
949
1287
1.48
1047
972
1425
1.64
1067
997
1576
1.81
1089
1024
1739
2.00
1112
1051
1916
2.20
1136
1079
2106
2.42
1161
1109
2309
2.66
1188
1139
2528
2.91
1.6
Rpm
Watts
Bhp
Rpm
1390
2471
2.84
1400
2623
3.02
2. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and
casing losses. See Table 13 for accessory/FIOP static pressure
information.
5. Extensive motor and drive testing on these units ensures that the full
bhp and watts range of the motor can be utilized with confidence.
Using your fan motors up to the watts or bhp rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your
Bryant representative for details.
—19—
0.8
1.0
Watts
Bhp
Rpm
Watts
1507
1.73
1139
1735
1648
1.90
1156
1880
1803
2.07
1175
2038
1970
2.27
1195
2209
2151
2.47
1217
2393
2345
2.70
1240
2590
2553
2.9
1.8
2.0
Watts
Bhp
Rpm
Watts
Bhp
2.00
2.16
2.34
2.54
2.75
2.98
Bhp