Bryant 581A Installation And Service Instructions Manual page 10

Single package rooftop electric cooling/gas heating units
Hide thumbs Also See for 581A:
Table of Contents

Advertisement

NOMINAL
VOLTAGE
UNIT
VOLTAGE
RANGE
581A
(3 Ph, 60
Min
Hz)
208/230
187
015
(Standard
IFM)
460
414
208/230
187
015
(Optional
IFM)
460
414
208/230
187
017
460
414
208/230
187
025
460
414
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and
Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percent voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Table 2 — Electrical Data
COMPRESSOR
No. 1
No. 2
Max
RLA
LRA
RLA
253
20.7
156
19.3
508
10
70
10
253
20.7
156
19.3
508
10
70
10
253
32.1
195
20.7
508
16.4
95
10
253
42
239
33.6
508
19.2
125
17.3
OFM
LRA
Qty
Hp
FLA (ea)
Hp
123
3
0.5
1.7
2.9
62
3
0.5
0.8
2.9
123
3
0.5
1.7
3.7
62
3
0.5
0.8
3.7
156
3
0.5
1.7
5.0
70
3
0.5
0.8
5.0
225
2
1
6.6
7.5
114
2
1
3.3
7.5
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
1371
=
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
—10—
POWER
COMBUSTION
IFM
EXHAUST
FAN MOTOR
FLA
FLA
LRA
FLA
8.8/
0.57
8.4
4.6
18.8
0.57
0.30
4.2
2.3
6.0
0.30
11.0/
0.57
10.5
4.6
18.8
0.57
0.30
4.8
2.3
6.0
0.30
15.8/
0.57
15.8
4.6
18.8
0.57
0.30
7.9
2.3
6.0
0.30
25.0/
0.57
25.0
4.6
18.8
0.57
0.30
13.0
2.3
6.0
0.30
3
3
7
457
POWER
SUPPLY
MCA
MOCP*
59/59
70/70
64/63
80/80
29
35
31
40
61/61
80/80
66/65
80/80
30
35
32
40
82/82
110/110
86/86
110/110
41
50
43
50
124/124
150/150
129/129
150/150
61
80
63
80