Bryant DuraPac 558F Installation & Service Instructions Manual
Bryant DuraPac 558F Installation & Service Instructions Manual

Bryant DuraPac 558F Installation & Service Instructions Manual

Single package rooftop electric heat/electric cooling unit
Hide thumbs Also See for DuraPac 558F:

Advertisement

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-20
I. Step 1 - Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . 1
III. Step 3 - Field Fabricate Ductwork . . . . . . . . . . . . . 9
V. Step 5 - Trap Condensate Drain . . . . . . . . . . . . . . . 9
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VIII. Step 8 - Install Outdoor-Air Hood. . . . . . . . . . . . . 14
IX. Step 9 - Install All Accessories . . . . . . . . . . . . . . 17
Dehumidification Package . . . . . . . . . . . . . . . . . . . 18
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20-26
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26-32
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 33,34
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing operations.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit and install lockout tag on disconnect switch.
Electrical shock could cause personal injury.
IMPORTANT: Units have high ambient operating limits. If
limits are exceeded, the unit will automatically lock the com-
pressor out of operation. Manual reset will be required to
restart the compressor.
installation, start-up and
service instructions
SINGLE PACKAGE ROOFTOP
ELECTRIC HEAT/ELECTRIC COOLING UNITS
Page
Cancels: New

INSTALLATION

I. STEP 1 - PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb or horizontal
adapter roof curb in accordance with instructions shipped
with the curb or horizontal adapter. Accessory roof curb and
horizontal adapter roof curb and information required to
field fabricate a roof curb or horizontal adapter roof curb are
shown in Fig. 1A, 1B and 2. Install insulation, cant strips,
roofing, and counter flashing as shown. Ductwork can be
secured to roof curb before unit is set in place.
IMPORTANT: The gasketing of the unit to the roof curb or
adapter roof curb is critical for a leak-proof seal. Install
gasket supplied with the roof curb or adapter roof curb as
shown in Fig. 1A and 1B. Improperly applied gasket can
result in air leaks and poor unit performance.
Curb or adapter roof curb should be level. This is necessary
to permit unit drain to function properly. Unit leveling toler-
ance is ±
1
/
in. per linear ft in any direction. Refer to Acces-
16
sory Roof Curb or Horizontal Adapter Roof Curb Installation
Instructions for additional information as required.
B. Alternate Unit Support
When the curb or adapter cannot be used, support unit with
sleepers using unit curb or adapter support area. If sleepers
cannot be used, support long sides of unit with a minimum of
3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 - RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright, and do not drop.
Use spreader bars over unit to prevent sling or cable dam-
age. Rollers may be used to move unit across a roof. Level by
using unit frame as a reference; leveling tolerance is ±
per linear ft in any direction. See Fig. 3 for additional infor-
mation. Unit weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as
shown in Fig. 3. Refer to rigging instructions on unit.
A. Positioning
Provide clearance around and above unit for airflow, safety,
and service access (Fig. 4-6).
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
B. Roof Mount
Check building codes for weight distribution requirements.
558F
DuraPac Series
Sizes 180-300
15 to 25 Tons
II 558F-180-1
6/15/02
1
/
in.
16

Advertisement

Table of Contents
loading

Summary of Contents for Bryant DuraPac 558F

  • Page 1: Table Of Contents

    installation, start-up and 558F service instructions DuraPac Series Sizes 180-300 SINGLE PACKAGE ROOFTOP 15 to 25 Tons ELECTRIC HEAT/ELECTRIC COOLING UNITS Cancels: New II 558F-180-1 6/15/02 CONTENTS INSTALLATION Page I. STEP 1 — PROVIDE UNIT SUPPORT SAFETY CONSIDERATIONS ......1 A.
  • Page 2 — —...
  • Page 3 — —...
  • Page 4 DIMENSIONS MAXIMUM UNIT SHIPPING WEIGHT 558F Ft-in. Ft-in. 1725 6-11 2121 4- 0 1219 1785 6-11 2121 3-10 1168 1905 6-11 2121 3- 7 1092 NOTE: For preassembled horizontal adapter roof curb part no. 2255 1023 6-11 2121 3- 5 1041 CRRFCURB013A00, the accessory kit includes a factory-designed, high-static,...
  • Page 5 — —...
  • Page 6 — —...
  • Page 7 — —...
  • Page 8 Table 1 — Physical Data UNIT 558F NOMINAL CAPACITY (tons) OPERATING WEIGHT For Operating Weights see Fig. 4-6. COMPRESSOR/MANUFACTURER Scroll/Copeland Quantity...Model (Ckt 1/Ckt 2) 1...ZR94KC, 1...ZR108KC, 1...ZR125KC, 1...ZRU140KC*, 1...ZR72KC 1...ZR94KC 1...ZR108KC 1...ZR144KC Stages of Capacity Control (%) 60/40 55/45 55/45 50/50 Number of Refrigerant Circuits Oil (oz) (Ckt 1, Ckt 2)
  • Page 9: Step 3 - Field Fabricate Ductwork

    III. STEP 3 — FIELD FABRICATE DUCTWORK IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS Secure all ducts to building structure. Use flexible duct con- Unit is shipped for through-the-bottom duct connections. nectors between unit and ducts as required. Insulate and Ductwork openings are shown in Fig.
  • Page 10: Step 6 - Make Electrical Connections

    B. Field Control Wiring Install a Bryant-approved accessory thermostat assembly or light commercial thermidistat for units equipped with Per- fect Humidity™ Dehumidification option, according to the Fig. 11 — Make Electrical Connections installation instructions included with the accessory.
  • Page 11 Table 2 — Electrical Data COMPRESSOR VOLTAGE POWER ELECTRIC POWER SUPPLY NOMINAL RANGE EXHAUST HEAT* UNIT No. 1 No. 1A No. 2 VOLTAGE 558F (3 Ph, 60 Hz) Max RLA LRA RLA LRA RLA LRA Qty Hp FLA LRA MOCP† (ea) —...
  • Page 12 Table 2 — Electrical Data (cont) COMPRESSOR VOLTAGE POWER ELECTRIC POWER SUPPLY NOMINAL RANGE EXHAUST HEAT* UNIT No. 1 No. 1A No. 2 VOLTAGE 558F (3 Ph, 60 Hz) Max RLA LRA RLA LRA RLA LRA Qty Hp FLA LRA MOCP†...
  • Page 13: Step 7 - Make Outdoor-Air Inlet Adjustments

    C. Optional Non-Fused Disconnect VII. STEP 7 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS On units with the optional non-fused disconnect, incoming A. Manual Outdoor-Air Damper power will be wired into the disconnect switch. Refer to All units (except those equipped with a factory-installed Fig.
  • Page 14: Step 8 - Install Outdoor-Air Hood

    Table 3 — Heat Anticipator Settings 6. Match notches in hood top panel to unit top panel screws. Insert hood flange between unit top panel UNIT UNIT flange and unit. Tighten screws. STAGE 1 STAGE 2 558F VOLTAGES 7. Hold hood side panel flanges flat against unit, and 26/34 install screws removed in Step 5.
  • Page 15 SENSOR OUTSIDE AIR SENSOR COVER Fig. 20 — Seal Strip Location (Air Hood Cross-Sectional View) BAFFLE (300 ONLY) Fig. 22 — Outdoor-Air Sensor Location MOUNTING SCREW LOWER FILTER RETAINER FILTER SUPPORT BRACKET SENSOR WIRING CONNECTIONS MOUNTING HOOD SIDE SCREW PANELS (2) HOOD TOP PANEL BAFFLE...
  • Page 16 F. Mechanical Cooling Lockout Fig. 17. When the OAT is above this set point, the damper is limited to minimum position setting. Determine the outdoor-air temperature at which the mechanical cooling (compressors) will be disabled. Locate the If a potentiometer fails, its setting will default to the values mechanical cooling lockout (MECH CLG LOCKOUT) poten- in Table 6.
  • Page 17: Step 9 - Install All Accessories

    2. Locate the minimum position (MIN POS) potentiome- See Fig. 26 for baffle details. Use 20-gage, galvanized sheet ter. Turn the potentiometer full CCW to fully close the metal, or similar corrosion-resistant metal for baffles. Use outdoor air dampers. Turn the potentiometer gradu- field-supplied screws to attach baffles to unit.
  • Page 18: Step 10 - Install Humidity Control Accessory For Optional Perfect Humidity™ Dehumidification Package

    Screws should Perfect Humidity dehumidification package operation can be -in. diameter and -in. long. Drill required screw holes controlled by field installation of a Bryant-approved for mounting baffles. humidistat or light commercial thermidistat. To install the control, perform the following procedure: CAUTION: To avoid damage to the refrigerant 1.
  • Page 19 SENSOR SENSOR SENSOR LOCATION LOCATION LOCATION HAIRPIN END HAIRPIN END HAIRPIN END 558F180 558F210 558F240 NOTE: All sensors are located on the eighth hairpin up from the NOTE: All sensors are located on the eighth hairpin up from the bottom. bottom.
  • Page 20: Start-Up

    If the suction pressure does not drop and the discharge pres- sure does not rise to normal levels: 1. Note that the evaporator fan is probably also rotating in the wrong direction. 2. Turn off power to the unit. 3. Reverse any two of the incoming power leads. 4.
  • Page 21 ROOFTOP UNIT LEGEND — Light Commercial Thermidistat LLSV — Liquid Line Solenoid Valve — Low-Pressure Switch — Terminal Block DEHUM TSTAT WIRES 24 V FROM PERFECT HUMIDITY LLSV FIELD-SUPPLIED RELAY HN61KK324 FROM PERFECT HUMIDITY LLSV Fig. 31 — Typical Perfect Humidity™ Dehumidification Package Thermidistat Wiring Schematic Table 8 —...
  • Page 22 Table 9 — Fan Performance — 558F210* AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts Watts 5,500 1.99 1675 2.29 1922 2.59 2177 2.90 2441 3.22 2712 1027 3.56 2990 6,000 2.38 2005 2.68 2257 2.99 2516 3.31...
  • Page 23 Fan Motor Performance on page 24 for additional information. below for accessory/factory-installed option static pressure information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant 2. Extensive motor and electrical testing on these units ensures that the full representative for details.
  • Page 24 Table 13 — Fan Rpm at Motor Pulley Settings* MOTOR PULLEY TURNS OPEN UNIT 558F 180† †† †† †† †† 1021 1002 180** †† †† †† †† 1200 1178 1156 1134 1112 1091 1069 1047 1025 210† †† †† 1095 1077 1058 1040...
  • Page 25 NOTE: Compressor no. 2 cannot be energized unless there is from the factory, both Perfect Humidity dehumidification cir- a signal for Y2 from the space thermostat. cuits are always energized. 4. If compressor no. 2 is energized, and the Y2 signal If Perfect Humidity circuit modulation is desired, a field- from the thermostat is satisfied, compressors 1 and 2 installed, wall-mounted humidistat or light commercial ther-...
  • Page 26: Service

    As the refrigerant leaves the evaporator, the refrigerant II. LUBRICATION passes a subcooler control low-pressure switch (S-LPS1 for A. Compressors circuit 1 or S-LPS2 for circuit 2) in the suction line. This low- Each compressor is charged with the correct amount of oil at pressure switch will deactivate the Perfect Humidity™...
  • Page 27 IV. EVAPORATOR FAN SERVICE AND REPLACEMENT The 558F units use a fan motor mounting system that fea- tures a slide-out motor mounting plate. To replace or service the motor, slide out the bracket. See Fig. 34. 1. Remove the evaporator-fan access panel and the heating control access panel.
  • Page 28 non-critical and flashes the appropriate code. If a non-critical sensor fault occurs (i.e., outdoor air humidity), the EconoMi$er automatically reconfigures its control strategy to a more appropriate mode. If a critical sensor fault occurs (i.e., supply air sensor), the EconoMi$er reverts to a safe mode of operation until the sensor problem is resolved.
  • Page 29 See Fig. 38 and 39. XIV. REPLACEMENT PARTS A complete list of replacement parts may be obtained from LIQUID PRESSURE AT LIQUID VALVE (PSIG) any Bryant distributor upon request. Fig. 37 — Cooling Charging Chart — —...
  • Page 30 XV. ECONOMI$ER LEDs filter and drive access. One door is provided for control box access. The control box access door is interlocked with the The EconoMi$er control module has an LED for diagnostic non-fused disconnect which must be in the OFF position to purposes.
  • Page 31 ELECTRIC HEAT 208/240 v Amps 200/230 v kW 71.3/82.3 25.7/34.2 117/135 42.2/56.1 156/180 56.2/74.8 Fig. 38 — Typical Wiring Schematic (558F240, 208/230-3-60 Shown) — —...
  • Page 32 Fig. 38 — Typical Wiring Schematic (558F240, 208/230-3-60 Shown) (cont) Fig. 39 — Typical Component Arrangement (558F240 Shown) — —...
  • Page 33: Troubleshooting

    TROUBLESHOOTING Refer to Tables 17-19 for troubleshooting details. Table 17 — Cooling Service Analysis PROBLEM CAUSE REMEDY Compressor and Power failure. Call power company. condenser fan Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. will not start. Defective thermostat, contactor, transformer, or control Replace component.
  • Page 34 Table 18 — EconoMi$er Troubleshooting PROBLEM POTENTIAL CAUSE REMEDY Damper Does Not Indoor (Evaporator) Fan is Check to ensure that 24 vac is present at Terminal C1 (Common Power) Open on the IFC (Indoor [Evaporator] Fan Contactor) or that 24 vac is present at the IFO (Indoor [Evaporator] Fan On) terminal.
  • Page 35: Index

    INDEX Access panels Mounting Air quantity limits Compressor Changeover set points Unit Charging chart, refrigerant Operating sequence Clearance Cooling sensor EconoMi$er 24, 25 Settings Heating 24, 25 Compressor Perfect Humidity 25, 26 Lockout Outdoor air hood 14, 15 Lubrication Outdoor air inlet screens Mounting Cleaning Rotation...
  • Page 38 Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG 1-800-962-9212 [ ] Packaged Service Training [ ] Classroom Service Training Copyright 2002 Bryant Heating & Cooling Systems CATALOG NO. 5355-811...
  • Page 40: Start-Up Checklist

    VERIFY REFRIGERANT CHARGE USING CHARGING CHART ON PAGE 29. GENERAL ECONOMI$ER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS (IF SO EQUIPPED) VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES CL-1 Copyright 2002 Bryant Heating & Cooling Systems CATALOG NO. 5355-811...

This manual is also suitable for:

Durapac series

Table of Contents