Grounding Cable in Facility DC Power Environments
The grounding cable satisfies an enclosure-to-enclosure grounding requirement in
facility DC power environments. Each type of bus bar supports a different number of
enclosures; therefore, each facility DC cable option kit contains a grounding cable to
support the appropriate number of enclosures.
WARNING: If using facility DC power, cables must be installed by a licensed
electrician or trained service personnel familiar with high-power circuitry.
To connect the grounding cable:
1. Insert the mounting screw through the grounding cable lead and into the
enclosure (1).
2. Tighten the mounting screw to secure the grounding cable to the enclosure (2).
Figure 4-10: Connecting a grounding cable (power and
management cabling removed for clarity)
3. Repeat steps 1 and 2 as needed for the configuration until all enclosures in the
rack are connected by the grounding cable.
4. Connect the lower end of the grounding cable to the facility grounding
connection.