Relay Interface Module; Figure 6-4. Relay Interface Module - Eaton Powerware 9315 Operation Manual

200–300 kva ups
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

Using Features and Options

6.6 Relay Interface Module

An optional RIM uses relay contact closures to indicate the operating status and alarm
condition of the UPS system. A maximum of two monitoring accessories (RMPs, RIMs, or
SCMs) can be installed. See Table 6-1 on page 6-4 for the number of accessories
permitted. Figure 6-4 shows the RIM with its four 15-pin connectors labeled J1 through J4.
The RIM can provide the following signals:
UPS AVAILABLE
UPS OFF LINE
BATTERY WEAK
UTILITY FAILURE
6-6

Figure 6-4. Relay Interface Module

Pins 1 and 12
Pins 3 and 13
Pins 5 and 14
Pins 6 and 15
EATON Powerware
9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com
®
Contacts are closed when the UPS is operating in
Normal mode or ready to supply the load.
Contacts are open when the UPS is offline.
Contacts are closed when the UPS is operating in
Normal mode.
Contacts are closed when approximately two
minutes of battery time is remaining, before the
critical load is lost.
Contacts are closed when Utility Failure is detected.