Performing Preventive Maintenance - Eaton Powerware 9315 Operation Manual

200–300 kva ups
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

Maintaining the UPS System
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal
of batteries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,
lead-acid batteries and must be disposed of properly. For more information, contact your local
recycling or hazardous waste center.
Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d'incendie. Suivre les
précautions qui s'imposent.
Pour le remplacement, utiliser le même nombre et modéle des batteries.
L'élimination des batteries est règlementée. Consulter les codes locaux à cet effet.

8.2 Performing Preventive Maintenance

The UPS requires very little preventive maintenance. However, the UPS should be inspected
periodically to verify that it is operating normally and that the batteries are in good
condition.
Perform the following checks DAILY:
Check the area surrounding the UPS. Ensure the area is not cluttered, allowing free
access to the UPS.
Ensure the air intakes (vents on the front doors) and exhaust opening (on top of the
UPS cabinet) are not blocked.
Ensure the operating environment is within the parameters specified in Chapter 9,
"Product Specifications."
Ensure the UPS is in Normal mode (Normal status indicator is lit). If an alarm lamp is lit
or the Normal status indicator is not lit, contact your Eaton service representative.
Perform the following checks MONTHLY:
Ensure all status indicator lamps are operative. (Press the
simultaneously to test the lamps.)
Monitor system parameters as described in Chapter 5, "Using the Monitor Panel."
Check the air filters (located behind the front doors) and replace them as necessary (the
filter size is 16"
Record the results of your checks and any corrective actions in a suitable log.
8-2
20"
1").
×
×
EATON Powerware
9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com
®
W A R N I N G
C A U T I O N
A V E R T I S S E M E N T !
and
buttons

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents