When connecting a mounting type resistor or braking resistor unit, set system constant L3-04 to 0 (stall prevention disabled during deceleration). If oper-
ating without changing the constant, motor does not stop at set deceleration time.
2.
When connecting mounting type braking resistor, set system constant L8-01 to 1 (braking resistor protection enabled).
3.
Load factor during deceleration to stop a load with constant torque. With constant output or continuous regenerative braking, the load factor is smaller
than the specified value.
4.
Resistance value per one braking unit. Select a resistance value that is larger than connectable minimum resistance value to obtain enough braking
torque.
5.
For an application with large regenerative power such as hoisting, the braking torque or other items may exceed the capacity of a braking unit with a
braking resistor in a standard combination (can result in capacity overload). Contact your OMRON representatives when the braking torque or any other