5.6 Communication Writing Control

cmwt
(CMWT)
TIPS
No operation for ten seconds
at the adjustment level
causes the product to return
to the current value display
mode at the operation level
automatically.
Communication writing can be enabled or disabled.
Communication reading is always enabled, irrespective of this parameter setting.
Parameter
Set value
off
cmwt
on
Procedure
A.
Press the L key at the operation level to move
to the adjustment level.
"r" will appear on the level indicator, indicating
the product has entered the adjustment level.
B.
Press the S key to display the set value of the
parameter on the main indicator.
The current set value will appear on the main
indicator.
C.
Press the S key again.
The set value will start blinking, indication the
product is in the change state.
D.
Use the
key to change the set value.
/
ZERO
E.
Press the M key to save the change.
The change is saved and then the main indicator
returns to the parameter display mode.
F.
Press the L key to return to the operation
level.

5.6 Communication Writing Control

Description
Communication writing is
disabled.
Communication writing is
enabled.
Adjustment level
L
0cmwt
T
r
"r" appears.
S
off
T
0c
a
"SV" is illuminated.
S
0coff
T
a
/
on
T
ZERO
0co
a
M
0cmwt
T
a
L
123$5
T
a
47